- Product Certifications:
- UL || CSA || NOM
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Net Weight:
- 29 lb(US)
- Mounting Height:
- 9 in
- Suitability For Isolation:
- yes IEC 60947-2
- Product Name:
- PowerPact M
- Device Application:
- distribution
- Quality Labels:
- CE
- Rohs Exemption Information:
- Yes
- Utilisation Category:
- category A
- Breaking Capacity Code:
- J
- Pvc Free:
- Yes
- Circularity Profile:
- ENVEOLI2206030EN
- Range:
- PowerPact
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 13123.36 ft (4000 m) with derating
- Magnetic Tripping Current:
- 1600-8000 A
- Ip Degree Of Protection:
- IP40
- Continuous Current Rating:
- 0.8
- Product Or Component Type:
- circuit breaker
- Mounting Mode:
- I-Line bracket)
- Ambient Air Temperature For Operation:
- -25-70 °C
- [Ics] Rated Service Breaking Capacity:
- 35 kA 240 V AC 50/60 Hz IEC 60947-2 || 25 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Quantity Per Set:
- 1
- Line Rated Current:
- 300-800 A
- Control Type:
- operating handle
- Sustainable Offer Status:
- Green Premium product
- Depth:
- 8.05 in
- Pollution Degree:
- 3 IEC 60947-1
- Long Time Pick-Up Adjustment Range:
- 300...800 A
- Electrical Connection:
- I-Line connection, line || lugs, load
- Poles Description:
- 3P
- Mercury Free:
- Yes
- Trip Unit Technology:
- electronic, basic, ET 1.0,
- Width:
- 8.27 in
- Mounting Support:
- bracket
- Accessory / Separate Part Type:
- communication module
- Local Signalling:
- 1 trip indicator green)
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Trip Unit Name:
- ET 1.0
- Color:
- Black
- Tightening Torque:
- 50-50 N.m 95-240 mm² (3 x AWG 3/0...3 x 500 kcmil)
- Environmental Disclosure:
- ENVPEP2206030EN
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Network Frequency:
- 50/60 Hz
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Awg Gauge:
- 3 x AWG 3/0...3 x 500 kcmil aluminium/copper
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Eu Rohs Directive:
- Compliant with Exemptions
- Wire Stripping Length:
- 25 mm
- Breaking Capacity:
- AIR 100 kA 240 V AC 50/60 Hz UL 489 || AIR 65 kA 480 V AC 50/60 Hz UL 489 || AIR 25 kA 600 V AC 50/60 Hz UL 489 || Icu 65 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 50 kA 380/415 V AC 50/60 Hz IEC 60947-2
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz UL 489
- Ambient Air Temperature For Storage:
- -50-85 °C
- Height:
- 12.86 in
- Terminal Identifier:
- AL800M23K
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 voltage release MN or MX plug-in)
- Communication Interface:
- Modbus
- Circuit Breaker Application:
- HACR rated