Schneider Electric

Schneider Electric PGL36060CU31A Molded Case Circuit Breaker 600V 600A

(No reviews yet) Write a Review
SKU:
PGL36060CU31A
UPC:
785901678298
Condition:
New
Width:
8.27 in
[Ics] Rated Service Breaking Capacity:
25 kA 240 V AC 50/60 Hz IEC 60947-2 || 20 kA 380/415 V AC 50/60 Hz IEC 60947-2
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Ambient Air Temperature For Storage:
-50-85 °C
Sustainable Offer Status:
Green Premium product
Rohs Exemption Information:
Yes
Terminal Identifier:
AL800M23K
Awg Gauge:
3 x AWG 3/0...500 kcmil aluminium/copper
Quantity Per Set:
1
Trip Unit Technology:
electronic, standard, MicroLogic 3.0, LI
Continuous Current Rating:
1
Tightening Torque:
50-50 N.m 95-240 mm² (3 x AWG 3/0...500 kcmil) || 1.0-1.3 N.m
Environmental Disclosure:
ENVPEP2206033EN
Local Signalling:
overload 1 1 LED amber) || 1 trip indicator green)
Mercury Free:
Yes
Wire Stripping Length:
25 mm
Warranty:
18 months
[Ue] Rated Operational Voltage:
600 V AC 50/60 Hz UL 489
Net Weight:
32 lb(US)
Number Of Slots:
2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
Trip Unit Name:
MicroLogic 3.0
Height:
12.86 in
Ip Degree Of Protection:
front cover IP40
Product Certifications:
UL || CSA || NOM
Circularity Profile:
ENVEOLI2206033EN
[Ui] Rated Insulation Voltage:
750 V IEC 60947-2
Eu Rohs Directive:
Compliant with Exemptions
Circuit Breaker Application:
HACR rated
Line Rated Current:
600-600 A
Pollution Degree:
3 IEC 60947-1
Control Type:
toggle
Breaking Capacity:
AIR 65 kA 240 V AC 50/60 Hz UL 489 || AIR 35 kA 480 V AC 50/60 Hz UL 489 || AIR 18 kA 600 V AC 50/60 Hz UL 489 || Icu 50 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 35 kA 380/415 V AC 50/60 Hz IEC 60947-2
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 13123.36 ft (4000 m) with derating
Product Name:
PowerPact P
Device Application:
distribution
Range:
PowerPact
Poles Description:
3P
Product Or Component Type:
circuit breaker
Depth:
8.05 in
Electrical Connection:
lugs, load || lugs, line
Ambient Air Temperature For Operation:
-2-70 °C
Network Frequency:
50/60 Hz
Pvc Free:
Yes
Quality Labels:
CE
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Standards:
UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
Breaking Capacity Code:
G
Long Time Pick-Up Adjustment Range:
0.4...1 x Ir
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
Brochure:
View
Catalog:
View
Datasheet:
View
$21,510.00

Description

PowerPacT P-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT P-Frame circuit breakers have either a fixed long time electronic trip unit, ET 1.0I, or Micrologic trip units. Micrologic trip units can be interchanged in the field to allow for maximum flexibility; the basic electronic trip unit doesn't have that interchangeability. This circuit breaker has a Micrologic Interchangeable Standard with a 3.0 trip unit and an LI function. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT P circuit breakers are available in 2, 3, and 4-pole unit mount, I-Line, or drawout construction. This unit has lugs on both the line and load sides. This PowerPacT P, 600A, 3 pole, circuit breaker has an interrupting rating of 18kA at 600VAC. This circuit breaker has a continuous current rating of 100%. PowerPacT P circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked. For use on load end of circuit breaker only. For use in UL 508 Industrial Control applications. For use in UL 1995/CSA C22.2 No.
View AllClose