- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Mercury Free:
- Yes
- Terminal Identifier:
- AL800M23K
- Long Time Pick-Up Adjustment Range:
- 0.4...1 x Ir
- Ambient Air Temperature For Storage:
- -50-85 °C
- Height:
- 12.86 in
- Breaking Capacity Code:
- G
- Product Name:
- PowerPact P
- Tightening Torque:
- 50-50 N.m 95-240 mm² (3 x AWG 3/0...500 kcmil) || 1.0-1.3 N.m
- Circuit Breaker Application:
- HACR rated
- Continuous Current Rating:
- 1
- Ip Degree Of Protection:
- front cover IP40
- Range:
- PowerPact
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Accessory / Separate Part Type:
- motor operator 24...30 V DC
- Device Application:
- distribution
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Environmental Disclosure:
- ENVPEP2206033EN
- Quantity Per Set:
- 1
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Product Or Component Type:
- circuit breaker
- Electrical Connection:
- lugs, load || lugs, line
- Quality Labels:
- CE
- Warranty:
- 18 months
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Network Frequency:
- 50/60 Hz
- Pvc Free:
- Yes
- Rohs Exemption Information:
- Yes
- Line Rated Current:
- 800-800 A
- Trip Unit Name:
- MicroLogic 5.0
- Circularity Profile:
- ENVEOLI2206033EN
- Pollution Degree:
- 3 IEC 60947-1
- Control Type:
- motor mechanism
- Ambient Air Temperature For Operation:
- -2-70 °C
- Sustainable Offer Status:
- Green Premium product
- Product Certifications:
- UL || CSA || NOM
- Eu Rohs Directive:
- Compliant with Exemptions
- Wire Stripping Length:
- 25 mm
- Breaking Capacity:
- AIR 65 kA 240 V AC 50/60 Hz UL 489 || AIR 35 kA 480 V AC 50/60 Hz UL 489 || AIR 18 kA 600 V AC 50/60 Hz UL 489 || Icu 50 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 35 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Local Signalling:
- overload 1 1 LED amber) || 1 trip indicator green)
- Trip Unit Technology:
- electronic, standard, MicroLogic 5.0, LSI
- [Ics] Rated Service Breaking Capacity:
- 25 kA 240 V AC 50/60 Hz IEC 60947-2 || 20 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Net Weight:
- 32 lb(US)
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz UL 489
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 13123.36 ft (4000 m) with derating
- Awg Gauge:
- 3 x AWG 3/0...500 kcmil aluminium/copper
- Depth:
- 8.05 in
- Poles Description:
- 3P
- Width:
- 8.27 in