- Continuous Current Rating:
- 0.8
- Terminal Identifier:
- AL1200P25K
- Product Or Component Type:
- circuit breaker
- Ip Degree Of Protection:
- front cover IP40
- Circularity Profile:
- ENVEOLI1407012EN
- Poles Description:
- 3P
- Trip Unit Technology:
- electronic, basic, ET 1.0I, I
- Width:
- 8.27 in
- Quantity Per Set:
- 1
- Net Weight:
- 32 lb(US)
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Local Signalling:
- 1 trip indicator green)
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 13123.36 ft (4000 m) with derating
- Ambient Air Temperature For Operation:
- -2-70 °C
- Breaking Capacity Code:
- L
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Mercury Free:
- Yes
- Device Application:
- distribution
- Depth:
- 8.05 in
- Circuit Breaker Application:
- HACR rated
- Product Certifications:
- UL || CSA || NOM
- Tightening Torque:
- 50-50 N.m 95-240 mm² (4 x AWG 3/0...500 kcmil) || 1.0-1.3 N.m
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Pollution Degree:
- 3 IEC 60947-1
- Mounting Mode:
- unit mount lug)
- Electrical Connection:
- lugs, line || lugs, load
- Warranty:
- 18 months
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Environmental Disclosure:
- ENVPEP1407012EN
- [Ics] Rated Service Breaking Capacity:
- 65 kA 240 V AC 50/60 Hz IEC 60947-2 || 45 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Network Frequency:
- 50/60 Hz
- Product Name:
- PowerPact P
- Quality Labels:
- CE
- Line Rated Current:
- 1000-1000 A
- Wire Stripping Length:
- 30 mm
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Awg Gauge:
- 4 x AWG 3/0...500 kcmil aluminium/copper
- Trip Unit Name:
- ET 1.0I
- Control Type:
- toggle
- Ambient Air Temperature For Storage:
- -50-85 °C
- Range:
- PowerPact
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Eu Rohs Directive:
- Compliant
- [Ue] Rated Operational Voltage:
- 480 V AC 50/60 Hz UL 489
- Rohs Exemption Information:
- Yes
- Mounting Support:
- lug
- Pvc Free:
- Yes
- Long Time Pick-Up Adjustment Range:
- 1 In
- Breaking Capacity:
- AIR 125 kA 240 V AC 50/60 Hz UL 489 || AIR 100 kA 480 V AC 50/60 Hz UL 489 || AIR 25 kA 600 V AC 50/60 Hz UL 489 || Icu 125 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 85 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Sustainable Offer Status:
- Green Premium product
- Height: