- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Control Type:
- without test button
- Measurement Accuracy:
- +/- 10 % of the full scale value
- Run-Up Delay At Power-Up:
- 0.5 s
- Mechanical Durability:
- 30000000 cycles
- [Us] Rated Supply Voltage:
- AC non self-powered
- Measurement Range:
- 1...10 A AC || 208...480 V AC
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- Ambient Air Temperature For Operation:
- -20-50 °C
- Supply Voltage Limits:
- 183-528 V AC
- Status Led:
- 1 LED Green power ON || 1 LED Yellow fault || 1 LED Yellow relay ON
- Maximum Measuring Cycle:
- 140 ms as true rms value
- Electrical Durability:
- 100000 cycles
- Shock Resistance:
- 15 gn 11 ms IEC 60255-21-1
- Input Current:
- 11 A permanent at 25 °C E1-L2 terminals || 50 A non repetitive < 1 s at 25 °C E1-L2 terminals
- Sustainable Offer Status:
- Green Premium product
- Relative Humidity:
- 95-95 % 55-55 °C IEC 60068-2-30
- Rohs Exemption Information:
- Yes
- Standards:
- IEC 60255-6
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Width:
- 35 mm
- [Ui] Rated Insulation Voltage:
- 400 V IEC 60664-1
- Reset Time:
- 2000 ms
- Electromagnetic Compatibility:
- emission standard for industrial environments IEC 61000-6-4 || emission standard for residential, commercial and light-industrial environments IEC 61000-6-3 || immunity for industrial environments NF EN/IEC 61000-6-2
- Output Contacts:
- 1 C/O
- Resistance Across Terminals:
- 0.01 Ohm E1-L2 terminals
- Circularity Profile:
- ENVEOLI1504008EN
- Relay Type:
- pump control relays
- Utilisation Category:
- AC-12 IEC 60947-5-1 || AC-13 IEC 60947-5-1 || AC-14 IEC 60947-5-1 || AC-15 IEC 60947-5-1 || DC-12 IEC 60947-5-1 || DC-13 IEC 60947-5-1
- Maximum Switching Voltage:
- 250 V AC/DC
- Operating Position:
- any position
- Response Time:
- < 300 ms (in the event of a fault)
- Operating Rate:
- <= 360 operations/hour full load
- Hysteresis:
- 5-5 % threshold
- Maximum Switching Current:
- 5 A AC/DC
- Switching Capacity In Va:
- 1250 VA
- Marking:
- CE : EMC 89/336/EEC || CE : 73/23/EEC
- Vibration Resistance:
- 0.35 mm 5-57.6 Hz)IEC 60068-2-6/IEC 60255-21-1 || 1 gn 57.6-150 Hz)IEC 60068-2-6/IEC 60255-21-1
- Measurement Error:
- 1 % by volt over the whole range || +/- 0.05 %/°C
- Tightening Torque:
- 0.6-1 N.m IEC 60947-1
- Relay Monitored Parameters:
- overcurrent and undercurrent control || phase sequence on 3-phase supply || phase failure on 3-phase supply
- Product Certifications:
- C-tick || CSA || GOST || UL || GL
- Relay Name:
- RM35BA
- Nominal Output Current:
- 0.208333333333333
- Repeat Accuracy:
- +/- 1 % input and measurement circuit || +/- 1 % time delay
- Connections - Terminals:
- screw terminals, 1 x 0.5...1 x 4 mm² AWG 20...AWG 11) solid without cable end || screw terminals, 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14) solid without cable end || screw terminals, 1 x 0.2...1 x 2.5 mm² AWG 24...AWG 12) flexible with cable end ||
- Insulation Resistance:
- > 500 MOhm 500 V DC between supply and relay output 60255-5 || > 500 MOhm 500 V DC between measurement and relay output 60664-1 || > 1 MOhm 500 V DC between supply and measurement 60255-5 || > 500 MOhm 500 V DC between supply and relay output 60664-1
- Overvoltage Category:
- III IEC 60664-1
- Control Circuit Voltage Limits:
- 15 % + 10 % Un
- Mercury Free:
- Yes
- Time Delay Type:
- adjustable 1...60 s, +/- 10 % Ti on energisation || adjustable 0.1...10 s, +/- 10 % Tt- time delay upon fault
- Minimum Switching Current:
- 10 mA 5 V DC
- Ip Degree Of Protection:
- IP20 IEC 60529 terminals) || IP30 IEC 60529 casing)
- Eu Rohs Directive:
- Pro-active compliance (Product out of EU RoHS legal scope)
- Maximum Power Consumption In Va:
- 5 VA AC
- Ambient Air Temperature For Storage:
- -40-70 °C
- China Rohs Regulation:
- X
- Dielectric Strength:
- 2 kV AC 50 Hz shock wave 4 kV)
- Supply Frequency:
- 50/60 Hz +/- 10 %
- Pollution Degree:
- 3 IEC 60664-1
- Product Specific Application:
- for 3-phase and single-phase pump
- Mounting Support:
- 35 mm symmetrical DIN rail conforming to IEC 60715
- Range Of Product:
- Harmony Control Relays
- Housing Material:
- self-extinguishing plastic
- Immunity To Microbreaks:
- 500 ms
- Environmental Disclosure:
- ENVPEP1504008EN
- Product Or Component Type:
- pump control relay
- Warranty:
- 18 months