Control Circuit Voltage Limits:
15 % + 10 % Un
Control Type:
without test button
Supply Voltage Limits:
102-308 V AC
Circularity Profile:
ENVEOLI1504008EN
Operating Position:
any position without derating
Maximum Switching Voltage:
250 V AC/DC
Measurement Accuracy:
+/- 10 % of the full scale value in input || +/- 10 % of the full scale value in time delay
Control Circuit Frequency:
40...70 Hz
Ip Degree Of Protection:
IP20 IEC 60529 terminals) || IP30 IEC 60529 casing)
Marking:
CE : 73/23/EEC || CE : EMC 89/336/EEC
California Proposition 65:
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Maximum Power Consumption In Va:
6 VA AC
Status Led:
1 LED Green power ON || 1 LED Yellow correct frequency (high R1) || 1 LED Yellow correct frequency (low R2)
Immunity To Microbreaks:
10 ms
Contacts Material:
cadmium free
Product Or Component Type:
frequency control relay
Input Frequency:
70 Hz
Tightening Torque:
0.6-1 N.m IEC 60947-1
Relay Type:
frequency control relays
Sustainable Offer Status:
Green Premium product
Output Contacts:
1 C/O + 1 C/O
Insulation Resistance:
> 500 MOhm 500 V DC between supply and relay output IEC 60255-5 || > 500 MOhm 500 V DC between measurement and relay output IEC 60664-1 || > 1 MOhm 500 V DC between supply and measurement IEC 60255-5 || > 500 MOhm 500 V DC between supply and relay ou
Relay Monitored Parameters:
overfrequency and underfrequency 50 or 60 Hz
Environmental Disclosure:
ENVPEP1504008EN
Threshold Setting:
-2...10 Hz || -10...2 Hz
Warranty:
18 months
Product Certifications:
GL || UL || CSA || C-tick || GOST
Range Of Product:
Harmony Control Relays
Shock Resistance:
15 gn 11 ms IEC 60255-21-1
Maximum Measuring Cycle:
200 ms measurement cycle as true rms value
Utilisation Category:
AC-12 IEC 60947-5-1 || AC-13 IEC 60947-5-1 || AC-14 IEC 60947-5-1 || AC-15 IEC 60947-5-1 || DC-12 IEC 60947-5-1 || DC-13 IEC 60947-5-1 || DC-14 IEC 60947-5-1
Eu Rohs Directive:
Pro-active compliance (Product out of EU RoHS legal scope)
Relay Name:
RM35HZ21FM
Repeat Accuracy:
+/- 0.5 % input and measurement circuit || +/- 0.5 % time delay
Measurement Range:
40...70 Hz frequency
Relative Humidity:
95-95 % 55-55 °C IEC 60068-2-30
Run-Up Delay At Power-Up:
0.5 s
Ambient Air Temperature For Storage:
-40-70 °C
Rohs Exemption Information:
Yes
Minimum Switching Current:
10 mA 5 V DC
Mercury Free:
Yes
Overvoltage Category:
III IEC 60664-1
Pollution Degree:
3 IEC 60664-1
Measurement Error:
+/- 0.05 %/°C with temperature variation || < +/- 1 % over the whole range with voltage variation
Electromagnetic Compatibility:
emission standard for industrial environments IEC 61000-6-4 || emission standard for residential, commercial and light-industrial environments IEC 61000-6-3 || immunity for industrial environments NF EN/IEC 61000-6-2
China Rohs Regulation:
X
Vibration Resistance:
0.35 mm 5-57.6 Hz)IEC 60068-2-6/IEC 60255-21-1 || 1 gn 57.6-150 Hz)IEC 60068-2-6/IEC 60255-21-1
Operating Rate:
<= 360 operations/hour full load
Hysteresis:
0.3-0.3 % fixed
Standards:
IEC 60255-6 || NF EN 60255-6
Width:
35 mm
Reset Time:
2000 ms time delay
Connections - Terminals:
screw terminals, 1 x 0.5...1 x 4 mm² AWG 20...AWG 11) solid without cable end || screw terminals, 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14) solid without cable end || screw terminals, 1 x 0.2...1 x 2.5 mm² AWG 24...AWG 12) flexible with cable end ||
Housing Material:
self-extinguishing plastic
Mounting Support:
35 mm symmetrical DIN rail conforming to IEC 60715
Supply Frequency:
50/60 Hz +/- 10 %
Non-Dissipating Shock Wave:
4 kV
Electrical Durability:
100000 cycles
Mechanical Durability:
30000000 cycles
[Us] Rated Supply Voltage:
120...277 V AC
[Us] Rated Supply Voltage:
AC non self-powered
Insulation:
no galvanic insulation between supply and measurement
[Ui] Rated Insulation Voltage:
400 V IEC 60664-1
Nominal Output Current:
0.208333333333333
Dielectric Test Voltage:
2 kV AC 50 Hz
Time Delay Type:
adjustable 0.1...10 s, +/- 10 % Tt- time delay upon fault
Switching Capacity In Va:
1250 VA
Ambient Air Temperature For Operation:
-20-50 °C
Catalog:
View
Datasheet:
View
  • Schneider Electric RM35HZ21FM Frequency Relay 40-60Hz 12-277Vac
  • Schneider Electric RM35HZ21FM Frequency Relay 40-60Hz 12-277Vac
  • Schneider Electric RM35HZ21FM Frequency Relay 40-60Hz 12-277Vac
$222.00

Description

This Harmony RM35-HZ control relay allows monitoring of frequency control. This modular control relay is ideal for monitoring of frequency variations in electrical power sources such as wind turbine and micro-power stations. It has one of market medium form-factors with 35mm width, allowing for a flexible and easy installation on DIN rail, using the same space as any modular 3-pole DIN device. It also offers a selectable memory function, integral LED for indicating control status, sealable cover, with simple and precise settings with screw trimmers. It provides an automatic detection of abnormal electrical values before they incur serious damage to machinery thus reducing your maintenance and downtime costs. Multi function controller for wide choice selected in hard-wired logic automated systems, ideal for refurbishment of old installations without using a PLC. 0 0 0 0 0 0 0 0 0 0 0 0 0
View AllClose