Schneider Electric RMNF22TB30 Nfc Control Relay 3-Phases
Schneider ElectricThis 3-phase control relay belongs to the Schneider Electric Harmony Control relays range. This 3-phase control relay is integrated with NFC technology which brings in digital operation instead of analog operation. This is a 8A multifunction 3-phase control relay which monitors 3-phase or 3-phase with Neutral network and has an adjustable time delay of 0.1s to 60min. With Harmony NFC App, different alarms can be combined using AND, OR and NOT logic to form unique monitoring combinations for the two relay outputs which are individually configurable. NFC 3-phase control relay is a single reference supporting 7 functions namely Phase loss, Phase sequence, Asymmetry, Undervoltage, Overvoltage, Under-frequency, and Over-frequency. The 3-phase control relay is IP20 (terminals), IP40 (housing), and IP40(front panel) protected. Furthermore, the 4 digit password enhances security by preventing unauthorized change of settings. This RMNF22 dimensions are 22.5mm (width) x 90mm (height) x 99mm (depth) and weighs 0.125Kg. 0 0 It conforms to international standard EN/IEC 60255-1 and certifications like UL, CSA, CE, CCC, EAC, and RCM. 0 It is sold as a single unit. 0 Monitoring and testing are now intuitive as exact fault conditions can be identified through front LEDs and analyze data with Harmony NFC App. This saves time and boosts efficiency. 0 0 0 0 0
- Software Designation:
- Zelio NFC downloadable from Google Play store)
- Net Weight:
- 0.125 kg
- Rohs Exemption Information:
- Yes
- Maximum Operating Frequency:
- 13.56 MHz
- Hysteresis:
- 3-3 % fixed phase failure detection
- Contacts Material:
- cadmium free
- Environmental Disclosure:
- ENVPEP1504008EN
- [Ith] Conventional Free Air Thermal Current:
- 0.333333333333333
- Product Compatibility:
- NFC enabled mobile device
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: Nickel compounds, which is known to the State of California to cause cancer, and Di-isodecyl phthalate (DIDP), which is known to the State of California to cause birth defects or other repr
- On-Load Factor:
- 1
- Ambient Air Temperature For Storage:
- -40-70 °C
- Maximum Measuring Cycle:
- 150 ms measurement cycle as true rms value
- [Us] Rated Supply Voltage:
- AC non self-powered
- Mechanical Durability:
- 10000000 cycles
- Depth:
- 99 mm
- Ambient Air Temperature For Operation:
- -20-60 °C
- Shock Resistance:
- 15 gn 11 ms) not in operation IEC 60068-2-27 || 5 gn 11 ms) in operation IEC 60068-2-27
- Response Time:
- <= 300 ms
- Product Certifications:
- CE || UL || CSA || CCC || EAC || RCM
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Switching Capacity In Va:
- 2000 VA
- Overvoltage Category:
- III IEC 60664-1 || III UL 508
- Sustainable Offer Status:
- Green Premium product
- Mounting Support:
- 35 mm DIN rail conforming to IEC 60715
- Pollution Degree:
- 3 IEC 60664-1 || 3 UL 508
- Eu Rohs Directive:
- Pro-active compliance (Product out of EU RoHS legal scope)
- Repeat Accuracy:
- +/- 0.5 % input circuit || +/- 3 % time delay
- Control Type:
- without test button
- Utilisation Category:
- AC-15 IEC 60947-5-1 || DC-13 IEC 60947-5-1 || AC-1 IEC 60947-4-1 || DC-1 IEC 60947-4-1
- Dielectric Test Voltage:
- 2.5 kV AC 50 Hz, 1 min IEC 60255-27
- Circularity Profile:
- ENVEOLI1504008EN
- Run-Up Delay At Power-Up:
- 650 ms
- Relative Humidity:
- 93-97 % 25-55 °C IEC 60068-2-30
- Connections - Terminals:
- screw terminals, 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14) solid without cable end || screw terminals, 2 x 0.5...2 x 1.5 mm² AWG 20...AWG 16) flexible with cable end || screw terminals, 1 x 0.5...1 x 3.3 mm² AWG 20...AWG 12) solid without cable end |
- Supply Voltage Limits:
- 166.4-576 V AC line to line || 96-332.4 V AC line to neutral
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Mercury Free:
- Yes
- Ip Degree Of Protection:
- IP20 IEC 60529 terminals) || IP40 IEC 60529 housing) || IP40 IEC 60529 front panel)
- Measurement Error:
- < 0.05 %/Hz with frequency variation || < 0.05 %/°C with temperature variation
- Electrical Durability:
- 100000 cycles
- Width:
- 22.5 mm
- Height:
- 90 mm
- Immunity To Microbreaks:
- 10 ms
- Standards:
- IEC 60255-1
- Product Or Component Type:
- 3-phase control relay
- Local Signalling:
- Un, green LED steady)power ON || R1, amber LED steady)relay energised || R1, amber LED blinking)timing in progress || R2, amber LED steady)relay energised || R2, amber LED blinking)timing in progress || PL, red LED steady)alarm phase failure triggere
- Directives:
- 2014/30/EU - electromagnetic compatibility || 2014/35/EU - low voltage directive || 2014/53/EU - radio equipment directive
- Output Contacts:
- 2 C/O
- [Ui] Rated Insulation Voltage:
- 400 V
- [Uimp] Rated Impulse Withstand Voltage:
- 4 kV 1.2/50 µs
- Measurement Range:
- 208...480 V AC
- Time Delay Type:
- on-delay 0.1 s...60 min || off-delay 0.1 s...60 min || adjustable 0.1 s...1 min
- Reset Time:
- 1500 ms at maximum voltage
- Contacts Type And Composition:
- 2 C/O
- Electromagnetic Compatibility:
- voltage dips and interruptions immunity test - test level: 70 % (25/30 cycles) conforming to IEC 61000-4-11 || electrostatic discharge - test level: 6 kV level 3 (contact discharge) conforming to IEC 61000-4-2 || radiated radio-frequency electromagne
- Vibration Resistance:
- 0.075 mm 10-58.1 Hz) not in operation IEC 60068-2-6 || 1 gn 58.1-150 Hz) not in operation IEC 60068-2-6 || 0.035 mm 10-58.1 Hz) in operation IEC 60068-2-6 || 0.5 gn 58.1-150 Hz) in operation IEC 60068-2-6
- Housing Material:
- self-extinguishing plastic
- Setting Accuracy Of Time Delay:
- +/- 3 % 10 s...60 min || +/- 300 ms 0...10 s
- Phase:
- 3 phase
- Mounting Position:
- any position
- Maximum Switching Voltage:
- 250 V AC
- Nominal Power:
- 0.0002 mW
- Insulation Resistance:
- > 100 MOhm 500 V DC IEC 60255-27
- Threshold Adjustment Voltage:
- 2...20 % of Un selected
- Relay Type:
- control relay
- China Rohs Regulation:
- X
- Relay Monitored Parameters:
- phase sequence || phase failure detection || overvoltage detection || undervoltage detection || overfrequency and underfrequency || asymmetry
- Tightening Torque:
- 0.6-1 N.m IEC 60947-1 || 5.3-8.8 lbf.in IEC 60947-1
- Operating System:
- Android
- Alarm Threshold:
- 166...576 V adjustable overvoltage and undervoltage detection (line to line) || 96...332 V adjustable overvoltage and undervoltage detection (line to neutral) || 5...150 V adjustable asymmetry || 45...66 Hz adjustable overfrequency or underfrequency
- Software Version:
- V4.4 and above
- Setting Accuracy Of The Switching Threshold:
- +/- (1.5 % + 1 V)
- Minimum Switching Current:
- 100 mA 6 V
- Supply Frequency:
- 50...60 Hz +/- 10 %
- Relay Name:
- RMNF22
- Range Of Product:
- Harmony Control Relays
- Maximum Switching Current:
- 8 A AC
- Power Consumption In Va:
- 4-4 VA 480 V AC 60 Hz
- Brochure:
- View
- Catalog:
- View
- Datasheet:
- View