Surge Withstand:
0.5 kV 1.2/50 µs IEC 61000-4-5
Marking:
CE
[Us] Rated Supply Voltage:
24 V DC non isolated +/- 20 %
Safety Reliability Data:
MTTFd = 32.9 years || B10d = 30437
Temperature Coefficient:
150 ppm/°C
Analogue Output Current:
-30-0 mA no input or input wire broken || 22-30 mA no input or input wire broken
Circularity Profile:
ENVEOLI1607005EN
Local Signalling:
for power ON LED (green)
Eu Rohs Directive:
Pro-active compliance (Product out of EU RoHS legal scope)
Ambient Air Temperature For Operation:
0-50 °C mounting side by side || 0-60 °C 2 cm spacing
Product Or Component Type:
converter for Universal Pt100 probes
Ip Degree Of Protection:
IP20 terminal block) || IP50 housing)
Analogue Input Type:
temperature probe 0...100 °C/32..212 °F Pt 100 2, 3 or 4 wires
Pollution Degree:
2 IEC 60664-1
Rohs Exemption Information:
Yes
Disturbance Radiated/Conducted:
CISPR 22 group 1 - class B || CISPR 11
Standards:
DIN 43760 || EN/IEC 60751 || EN/IEC 60947-1 || EN/IEC 60584-1
Analogue Output Voltage:
-15...-11 V no input or input wire broken || 11...15 V no input or input wire broken
Range Of Product:
Harmony Analog
Warranty:
18 months
Fixing Mode:
clip-on 35 mm symmetrical DIN rail) || fixed mounting plate)
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Vibration Resistance:
5 gn 10-100 Hz)IEC 60068-2-6
Current Consumption:
<= 40 mA voltage output || <= 60 mA current output
Fire Resistance:
850 °C IEC 60695-2-1 || 850 °C UL
Measurement Error:
+/- 0.5 % of full scale 3 or 4 wires)20 °C || +/- 1 % of full scale 2 wires)20 °C || +/- 10 % of full scale20 °C electromagnetic interference of 10 V/m)
Mercury Free:
Yes
Analogue Output Type:
current 0...20 mA <= 500 Ohm || current 4...20 mA <= 500 Ohm || voltage 0...10 V >= 100 kOhm
Clamping Connection Capacity:
1 x 2.5 mm² || 2 x 1.5 mm²
[Ui] Rated Insulation Voltage:
2000 V
Maximum Wiring Resistance:
0.2 Ohm 2 wires
Environmental Disclosure:
ENVPEP1607005EN
China Rohs Regulation:
X
Ambient Air Temperature For Storage:
-40-85 °C
Tightening Torque:
0.6-1.1 N.m
Product Certifications:
GL || UL || CSA
Protection Type:
reverse polarity protection on power supply || short-circuit protection on output || overvoltage protection on output (+/- 30 V) || reverse polarity protection on output
California Proposition 65:
WARNING: This product can expose you to chemicals including: Nickel compounds, which is known to the State of California to cause cancer, and Di-isodecyl phthalate (DIDP), which is known to the State of California to cause birth defects or other repr
Repeat Accuracy:
+/- 0.2 % full scale 20 °C || +/- 0.6 % full scale 60 °C
Electromagnetic Compatibility:
electrostatic discharge - test level: 6 kV level 3 (contact discharge) conforming to IEC 61000-4-2 || electrostatic discharge - test level: 8 kV level 3 (air discharge) conforming to IEC 61000-4-2
Net Weight:
0.12 kg
Sustainable Offer Status:
Green Premium product
Resistance To Fast Transients:
1 kV IEC 61000-4-4 on input-output) || 2 kV IEC 61000-4-4 on power supply)
Shock Resistance:
50 gn 11 ms IEC 60068-2-27
Catalog:
View
Datasheet:
View
  • Schneider Electric RMPT30BD Harmony Analogue Pt100 0-100C
  • Schneider Electric RMPT30BD Harmony Analogue Pt100 0-100C
  • Schneider Electric RMPT30BD Harmony Analogue Pt100 0-100C
$141.00

Description

This temperature transmitter is part of the range of Harmony Analog interfaces. It is designed to convert signal of Pt100 probe into standard electrical signal which is compatible with automation platforms, controllers. Its supply voltage is 24V DC, non isolated. It also allows the connection distance between a sensor and the measurement acquisition device to be increased. The cables used to connect the converters to process equipment (PLCs) are standard cables, which are more cost effective than extension cables or compensation cables suitable for low level signals for Pt100 probes or thermocouples. Conforming to IEC standards, UL and CSA certified, this converter is suitable for universal use. 0 0 0 0 0 0 0 0 0 0 0