- Shock Resistance:
- 30 gn 11 ms IEC 88 reference 2-27
- Absolute Maximum Input:
- +/- 7.5 V DC
- Conversion Time:
- 150 ms voltage 60 Hz || 170 ms voltage 50 Hz || 180 ms temperature probe 60 Hz 2 or 4 wires || 200 ms temperature probe 50 Hz 2 or 4 wires || 210 ms thermocouple with internal cold-junction compensation 60 Hz || 230 ms thermocouple with internal cold
- Eu Rohs Directive:
- Pro-active compliance (Product out of EU RoHS legal scope)
- Analogue Input Type:
- voltage +/- 80 mV || temperature probe -100...+260 °C Cu 10 2, 3 or 4 wires IEC || temperature probe -100...+450 °C Pt 100 2, 3 or 4 wires US/JIS || temperature probe -100...+450 °C Pt 1000 2, 3 or 4 wires US/JIS || temperature probe -200...+850 Â
- China Rohs Regulation:
- X
- Input Impedance:
- 10 MOhm +/- 80 mV
- Warranty:
- 18 months
- Measurement Resolution:
- 0.01 mV voltage || 0.1 °C or 0.1 °F temperature probe || 0.1 °C or 0.1 °F thermocouple
- Product Compatibility:
- mounting base STBXBA1000 || power distribution module STBPDT3100/3105
- Type Of Filter:
- single low pass input filter 25 Hz
- Absolute Accuracy Error:
- +/- 0.1 % of full scale 25 °C internal || +/- 0.15 % of full scale 25 °C external
- Analogue Input Resolution:
- 15 bits + sign
- Ambient Air Temperature For Operation:
- 0-70 °C
- Range Of Product:
- Modicon STB distributed I/O solution
- Mercury Free:
- Yes
- Operating Altitude:
- <= 6561.68 ft (2000 m)
- Fallback Status:
- state 0 basic NIMs || user configurable standard NIMs
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- Cold Swapping:
- yes
- Status Led:
- 1 LED (Green) module status (RDY) || 1 LED (Red) module error (ERR)
- Hot Swapping Fallback:
- yes for standard NIMs
- Maximum Supply Current For Sensors:
- 100 mA per input channels
- Data Format:
- EN 61131-2 || IEC 61131-2
- Measurement Accuracy:
- +/- 1 °C Ni 100 25 °C external || +/- 1 °C Ni 100 25 °C internal || +/- 1 °C Ni 1000 25 °C external || +/- 1 °C Ni 1000 25 °C internal || +/- 1 °C Pt 100 25 °C internal || +/- 1 °C Pt 1000 25 °C internal || +/- 1.75 °C thermocouple B wit
- Ambient Air Temperature For Storage:
- -40...185 °F without derating
- Pollution Degree:
- 2 IEC 60664-1
- Overvoltage Category:
- II
- Product Or Component Type:
- standard analog input kit
- Ambient Air Temperature For Operation:
- 32...140 °F without derating
- Addressing Requirement:
- 1 word for cold-junction compensation || 2 input words
- Kit Composition:
- STBART0200 module || STBXTS1100, 6-terminal screw type connector || STBXBA1000 base || STBXTS2100, 6-terminal spring clamp connector
- [Us] Rated Supply Voltage:
- 24 V DC
- Rohs Exemption Information:
- Yes
- Insulation Between Channels And Logic Bus:
- 1500 V for 1 minute
- Ip Degree Of Protection:
- IP20 conforming to IEC 61131-2 class 1
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Relative Humidity:
- 95-95 % 60-60 °C without condensation
- Ambient Air Temperature For Storage:
- -40-85 °C without derating
- Vibration Resistance:
- +/-0.35 mm 10-58 Hz || 3 gn 58-150 Hz 35 x 7.5 mm symmetrical DIN rail || 5 gn 58-150 Hz 35 x 15 mm symmetrical DIN rail
- Protection Type:
- short-circuit protection
- Maximum Wiring Resistance:
- 20 Ohm Cu 10 IEC/US/JIS 2 or 3 wires || 20 Ohm Ni 100 IEC/US/JIS 2 or 3 wires || 20 Ohm Pt 100 IEC/US/JIS 2 or 3 wires || 200 Ohm Ni 1000 IEC/US/JIS 2 or 3 wires || 200 Ohm Pt 1000 IEC/US/JIS 2 or 3 wires || 50 Ohm Cu 10 IEC/US/JIS 4 wires || 50 Ohm
- Supply:
- power distribution module
- Product Certifications:
- UL || FM Class 1 Division 2 || CSA || ATEX Cat 3G || C-tick
- Current Consumption:
- 30 mA 5 V DC logic bus
- Analogue Input Number:
- 2
- Marking:
- CE
- QN-QUOTE-REQUEST:
- true