analog input module, Modicon TM3, 4 temperature differential inputs, screw, 24V DC
- Lsb Value:
- 0.1 °C thermocouple
- Cross Talk:
- <= 1 LSB
- Current Consumption:
- 45 mA 5 V DC via bus connector || 50 mA 5 V DC via bus connector || 35 mA 24 V DC via external supply || 40 mA 24 V DC via external supply
- Ambient Air Temperature For Storage:
- -25-70 °C
- Permissible Continuous Overload:
- 13 V voltage || 40 mA current
- Ip Degree Of Protection:
- IP20
- Shock Resistance:
- 15 gn 11 ms
- Electrical Connection:
- 10 x 1.5 mm² removable screw terminal block pitch 3.81 mm for inputs and supply || 10 x 1.5 mm² removable screw terminal block pitch 3.81 mm for inputs
- Storage Altitude:
- 0-3000 m
- [Us] Rated Supply Voltage:
- 24 V DC
- Non-Linearity:
- +/- 0.2 %FS
- Depth:
- 70 mm
- Range Of Product:
- Modicon TM3
- Repeat Accuracy:
- +/-0.5 %FS
- Vibration Resistance:
- 3.5 mm 5-8.4 Hz DIN rail || 3 gn 8.4-150 Hz DIN rail
- Pollution Degree:
- 2
- Resistance To Conducted Disturbances:
- 10 V 0.15...80 MHz IEC 61000-4-6 || 3 V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) Marine specification (LR, ABS, DNV, GL)
- Supply Voltage Limits:
- 20.4-28.8 V
- Standards:
- IEC 61131-2
- Resistance To Fast Transients:
- 1 kV IEC 61000-4-4 I/O)
- Analogue Input Number:
- 4
- Surge Withstand:
- 1 kV power supply common mode IEC 61000-4-5 || 0.5 kV power supply differential mode IEC 61000-4-5 || 1 kV input common mode IEC 61000-4-5
- Marking:
- CE
- Input Impedance:
- >= 1 MOhm thermocouple
- Electromagnetic Emission:
- radiated emissions 40 dBμV/m QP class A 10 m)30-230 MHz IEC 55011 || radiated emissions 47 dBμV/m QP class A 10 m)230-1000 MHz IEC 55011
- Width:
- 23.6 mm
- Ambient Air Temperature For Operation:
- -10-55 °C horizontal installation || -10-35 °C vertical installation
- Sampling Duration:
- 100 ms thermocouple
- Local Signalling:
- for PWR 1 LED (green)
- Immunity To Microbreaks:
- 10 ms
- Resistance To Electromagnetic Fields:
- 10 V/m 80 MHz...1 GHz IEC 61000-4-3 || 3 V/m 1.4 GHz...2 GHz IEC 61000-4-3 || 1 V/m 2 GHz...3 GHz IEC 61000-4-3
- Insulation:
- between input and supply 1500 V AC || between input and internal logic 500 V AC
- Conversion Time:
- 100 ms + 100 ms per channel + 1 controller cycle time thermocouple
- Mounting Support:
- top hat type TH35-15 rail IEC 60715 || top hat type TH35-7.5 rail IEC 60715 || plate or panel with fixing kit
- Analogue Input Type:
- thermocouple - 200...1000 °C thermocouple J || thermocouple - 200...1300 °C thermocouple K || thermocouple 0...1760 °C thermocouple R || thermocouple 0...1760 °C thermocouple S || thermocouple 0...1820 °C thermocouple B || thermocouple - 200...4
- Product Certifications:
- CE || UKCA || RCM || EAC || cULus || cULus HazLoc
- Temperature Drift:
- +/- 0.01 %FS/°C
- Height:
- 90 mm
- Resistance To Electrostatic Discharge:
- 8 kV in air IEC 61000-4-2 || 4 kV on contact IEC 61000-4-2
- Operating Altitude:
- 0...6561.68 ft (0...2000 m)
- Analogue Input Resolution:
- 16 bits || 15 bits + sign
- Absolute Accuracy Error:
- +/- 0.2 % of full scale at 25 °C for thermocouple C 0...2315 °C || +/- 6 °C at 25 °C for thermocouple R, S 0...200 °C || +/- 0.2 % of full scale at 25 °C for thermocouple R, S 200...1760 °C || +/- 0.2 % of full scale at 25 °C for thermocouple
- Type Of Cable:
- twisted shielded pairs cable <30 m input
- Range Compatibility:
- Modicon M221 || Modicon M241 || Modicon M251 || Modicon M262
- Net Weight:
- 0.11 kg
- Product Or Component Type:
- analog input module
- Relative Humidity:
- 10-95 %, without condensation in operation) || 10-95 %, without condensation in storage)
- Catalog:
- View