4-channel analog input; Resistance measurement; Adjustable
Technical Data
- Number of analog inputs: 4
- Total number of channels (module): 4
- Type of signal: Potentiometer positions
- Configurable type of signal: yes
- Sensor connection: 4 x (2-conductor, 3-conductor, 4-conductor)
- Bit width: 4 x 16-bit data; 4 x 8-bit control/status (optional)
- Resolution (over entire range): 0.1 C (over the entire range); 0.01 C (-50 C ... 150 C; Pt1000, Ni1000)
- Conversion time (typ.): 100 ms
- Conversion time: Per channel: 100 ms (2-/4-wire connection), 200 ms (3-wire connection)
- Measuring error (25 C): 0.6 K (Pt100, Pt200, Pt500, Ni100, Ni120); 0.2 K (Pt1000, Ni1000); 0.3 ... 0.7 at resistance measurement
- Measuring current (typ.): 350 A
- Response time (max.): 3 s
- Sensor types: Pt100 (default setting), Pt200, Pt500, Pt1000, Ni100, Ni120, Ni1000 (TK6180 + TK5000), Potentiometer 0 Ohm ... 1.2 kOhm, 0 Ohm ... 5 kOhm
- Temperature range: -200 +850 C (Pt100, Pt200, Pt500, Pt1000), -60 +250 C (Ni100, Ni1000), -80 +260 C (Ni120)
- System supply voltage: DC 5 V; via data contacts
- Current consumption, system supply (5 V): 85 mA
- Field supply voltage: DC 24 V (-25 +30 %); via power jumper contacts (power supply via blade contact; transmission via spring contact)
- Isolation: 500 V system/supply
- Number of incoming power jumper contacts: 2
- Number of outgoing power jumper contacts: 2
Connection Data
- Connection technology: In-/Outputs: 16 x Push-in CAGE CLAMP<sup></sup>
- Connection type (1): Inputs/Outputs
- Solid conductor: 0.08 1.5 mm / 28 16 AWG
- Fine-stranded conductor: 0.25 1.5 mm / 22 16 AWG
- Strip length: 8 9 mm / 0.31 0.35 inch
Geometrical Data
- Width: 12 mm / 0.472 inch
- Height: 69 mm / 2.717 inch
- Height from upper-edge of DIN-35 rail: 61.8 mm / 2.433 inch
- Depth: 100 mm / 3.937 inch
Mechanical Data
- Type of mounting: DIN-35 rail
Material Data
- Color: light gray
- Housing material: Polycarbonate, polyamide 6.6
- Fire load: 0.000 MJ
- Weight: 49.000 g
- Conformity marking: CE
Environmental Requirements
- Surrounding air (operating) temperature: 0 55 C
- Surrounding air (storage) temperature: -40 85 C
- Protection class: IP20
- Degree of pollution (5): 2 per IEC 61131-2
- Operating altitude: 0 2000 m
- Mounting position: horizontal (standing/lying) or vertical
- Relative air humidity (no condensation): 95 %
- Vibration resistance: 4g per IEC 60068-2-6
- Shock resistance: 15g per IEC 60068-2-27
- EMC immunity to interference: acc. to EN 61000-6-1, EN 61000-6-2
- EMC emission of interference: acc. to EN 61000-6-3
- Exposure to pollutants: Per IEC 60068-2-42 and IEC 60068-2-43
- Permissible H<sub>2</sub>S contaminant concentration at a relative humidity <lt/> 75 %: 10 ppm
- Permissible SO<sub>2</sub> contaminant concentration at a relative humidity <lt/> 75 %: 25 ppm
Commercial data
- Packaging type: BOX
- Country of origin: DE
- GTIN: 4017332448635
- Customs Tariff No.: 85389099990
The WAGO 750 series standard analog input slice module, model 750-450, features four configurable analog inputs for RTD sensors (Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni1000) and potentiometers (0...1200? / 0...5000?) with a 0.1°C resolution and 100ms conversion time. It supports 2-wire, 3-wire, and 4-wire connections, operates on a 5V DC supply provided by the system, and uses Push-in spring CAGE CLAMP connections. The module is designed for DIN-35 rail mounting, has a width of 12mm, and is rated for ambient temperatures between 0°C and +55°C with an IP20 protection rating.
- color:
- Light gray
- conformity marking:
- CE
- connection technology inputs outputs:
- 16 x Push-in CAGE CLAMP
- connection type 1:
- Inputs/outputs
- conversion time:
- Per channel: ¤ 100 ms (2-/4-wire connection), ¤ 200 ms (3-wire connection)
- conversion time typ:
- 100 ms
- country of origin sales organisation germany:
- DE
- data width:
- 4 x 16-bit data: 4 x 8-bit control/status (optional)
- depth:
- 69 mm / 2.717 inch
- depth from upper edge of din rail:
- 61.8 mm / 2.433 inch
- emc emission of interference:
- Per EN 61000-6-3
- emc immunity to interference:
- Per EN 61000-6-1: EN 61000-6-2
- exposure to pollutants:
- Per IEC 60068-2-42 and IEC 60068-2-43
- fine stranded conductor:
- 0.25 1.5 mm / 22 16 AWG
- fire load:
- 0.824 MJ
- height:
- 100 mm / 3.937 inch
- housing material:
- Polycarbonate: polyamide 6.6
- isolation:
- 500 V system/field
- measured current typ:
- ¤ 350 A
- measurement error 25 c:
- ¤ 0.6 K (Pt100, Pt200, Pt500, Ni100, Ni120): ¤ 0.2 K (Pt1000, Ni1000): 0.3 0.7 for resistance measurement
- mounting position:
- Horizontal (standing/lying): vertical
- mounting type:
- DIN-35 rail
- number of analog inputs:
- 4
- number of incoming power jumper contacts:
- 2
- number of outgoing power jumper contacts:
- 2
- operating altitude:
- 0 2000 m
- packaging type:
- Box
- permissible h2s contaminant concentration at a relative humidity 75:
- 10 ppm
- permissible so2 contaminant concentration at a relative humidity 75:
- 25 ppm
- pollution degree 5:
- 2 per IEC 61131-2
- power consumption 5 v system supply:
- 85 mA
- protection type:
- IP20
- relative humidity without condensation:
- 0.95
- resolution over entire range:
- 0.1 C (over the entire range): 0.01 C (50 150 C: Pt1000, Ni1000)
- response time max:
- 3 s
- sensor connection:
- 4 x (2-wire, 3-wire, 4-wire)
- sensor types:
- Pt100: Configurable: Pt200, Pt500, Pt1000, Ni100, Ni120, Ni1000 (TK6180 + TK5000), Potentiometer: 10R 1k2, 10R 5k0
- shock resistance:
- 15g per IEC 60068-2-27
- signal type:
- Resistance measurement || Potentiometer positions
- signal type configurable:
- Yes
- solid conductor:
- 0.08 1.5 mm / 28 16 AWG
- strip length:
- 8 9 mm / 0.31 0.35 inch
- supply voltage field:
- 24 VDC (-25 +30 %): via power jumper contacts (power supply via blade contact: transmission via spring contact)
- supply voltage system:
- 5 VDC: via data contacts
- surrounding air temperature operation:
- 0 55 C
- surrounding air temperature storage:
- -40 85 C
- temperature range:
- -200 +850 C (Pt100, Pt200, Pt500, Pt1000), -60 +250 C (Ni100, Ni1000), -80 +260 C (Ni120)
- total number of channels module:
- 4
- vibration resistance:
- 4g per IEC 60068-2-6
- weight:
- 49.000 g
- width:
- 12 mm / 0.472 inch