4AIU/I Diff, light gray.
The WAGO 750 series standard analog input slice module (model 750-471) features four analog inputs that support various signal ranges (0-20mA, 4-20mA, 3.6-21mA, -20...+20mA, 0-10Vdc, -10...+10Vdc, -200...+200mVdc) with differential and isolated inputs, offering 16-bit resolution and a 5ms conversion time. It operates on a 5Vdc supply voltage provided by the system and includes spring CAGE CLAMP connections for secure wiring. The module is designed for DIN-35 rail mounting with a 12mm width, has an IP20 protection rating, and is suitable for ambient temperatures ranging from 0°C to +55°C.
- color:
- Light gray
- conformity marking:
- CE
- connection technology inputs outputs:
- 8 x CAGE CLAMP
- connection type 1:
- Inputs/outputs
- conversion time typ:
- 10 ms
- country of origin sales organisation germany:
- DE
- current carrying capacity power jumper contacts:
- 0.416666666666667
- data width:
- 4 x 16-bit data: 4 x 8-bit control/status (optional)
- depth:
- 69.8 mm / 2.748 inch
- depth from upper edge of din rail:
- 62.6 mm / 2.465 inch
- emc emission of interference:
- Per EN 61000-6-4, marine applications
- emc immunity to interference:
- Per EN 61000-6-2, marine applications
- exposure to pollutants:
- Per IEC 60068-2-42 and IEC 60068-2-43
- fine stranded conductor:
- 0.08 2.5 mm / 28 14 AWG
- fire load:
- 0.881 MJ
- height:
- 100 mm / 3.937 inch
- housing material:
- Polycarbonate: polyamide 6.6
- input resistance max:
- 120
- internal resistance:
- 100 k
- measurement error deviation max from the upper range value:
- 0.001
- measurement error deviation max of the upper range value 2:
- 0.003
- measurement error reference temperature:
- 25 C
- measurement error reference temperature 2:
- 25 C
- mounting position:
- Horizontal (standing/lying): vertical
- mounting type:
- DIN-35 rail
- number of analog inputs:
- 4
- number of incoming power jumper contacts:
- 2
- number of outgoing power jumper contacts:
- 2
- operating altitude:
- 0 2000 m
- packaging type:
- Box
- permissible h2s contaminant concentration at a relative humidity 75:
- 10 ppm
- permissible so2 contaminant concentration at a relative humidity 75:
- 25 ppm
- pollution degree 5:
- 2 per IEC 61131-2
- power consumption 5 v system supply:
- 100 mA
- protection type:
- IP20
- reference for measurement error:
- Input ranges
- reference for measurement error 2:
- 200 mV
- relative humidity without condensation:
- 0.95
- resolution bit:
- 16 bits
- sensor connection:
- 4 x (2-wire)
- shock resistance:
- 15g per IEC 60068-2-27
- signal characteristic:
- Differential
- signal type:
- Current || Voltage
- signal type configurable:
- Yes
- signal type current:
- 0 20 mADC: 4 20 mADC: 3.6 21 mADC: -20 +20 mADC
- solid conductor:
- 0.08 2.5 mm / 28 14 AWG
- strip length:
- 8 9 mm / 0.31 0.35 inch
- supply voltage field:
- 24 VDC: via power jumper contacts (power supply via blade contact: transmission via spring contact)
- supply voltage system:
- 5 VDC: via data contacts
- surrounding air temperature operation:
- 0 55 C
- surrounding air temperature storage:
- -40 85 C
- temperature error max of the upper range value:
- 0.01 %/K
- total number of channels module:
- 4
- vibration resistance:
- 4g per IEC 60068-2-6
- voltage signal type:
- 0 10 VDC: -10 +10 VDC: -0.2 +0.2 VDC
- weight:
- 51.199 g
- width:
- 12 mm / 0.472 inch