- color:
- Blue
- conformity marking:
- CE
- connection technology inputs outputs:
- 16 x CAGE CLAMP
- connection type 1:
- Inputs/outputs
- conversion time:
- 150 500 ms (per channel)
- conversion time typ:
- 325 ms
- country of origin sales organisation germany:
- DE
- current carrying capacity power jumper contacts:
- 0.0416666666666667
- data width:
- 2 x 16-bit data: 2 x 8-bit control/status (optional)
- depth:
- 67.8 mm / 2.669 inch
- depth from upper edge of din rail:
- 60.6 mm / 2.386 inch
- dielectric strength:
- 510 VAC/775 VDC: per EN 60870-2-1
- emc emission of interference:
- Per EN 61000-6-3, -4, EN 61131-2, EN 60255-26, marine applications, EN 60870-2-1, EN 61850-3
- emc immunity to interference:
- Per EN 61000-6-1, -2, EN 61131-2, marine applications, EN 60255-26, EN 60870-2-1, EN 61850-3, IEC 61000-6-5, IEEE 1613, VDEW: 1994
- ex guideline:
- EN/IEC 60079-0, -7, -11
- exposure to pollutants:
- Per IEC 60068-2-42 and IEC 60068-2-43
- fine stranded conductor:
- 0.25 2.5 mm / 24 14 AWG
- fire load:
- 1.249 MJ
- height:
- 100 mm / 3.937 inch
- housing material:
- Polycarbonate: polyamide 6.6
- intrinsic safety ex i:
- Yes
- isolation:
- 300 VAC system/field
- marking:
- ATEX/IECEx: II 3 (1) G Ex ec [ia Ga] IIC T4 Gc: II (1) D [Ex ia Da] IIIC: I (M1) [Ex ia Ma] I
- measured current typ:
- < 0.5 mA
- measurement error deviation max from the upper range value:
- 0.002
- measurement error reference temperature:
- 25 C
- mounting position:
- Horizontal (standing/lying): vertical
- mounting type:
- DIN-35 rail
- note:
- The analog output module must only be operated via 24 VDC Ex i XTR power supply (750-606/040-000)!General information (e.g., installation regulations) on explosion protection is available in the WAGO I/O System 750 XTR manuals!
- number of analog inputs:
- 2
- number of incoming power jumper contacts:
- 2
- number of outgoing power jumper contacts:
- 2
- operating altitude:
- Without temperature derating: 0 2000 m: with temperature derating: 2000 5000 m (0.5 K/100 m): 5000 m (max.)
- packaging type:
- Box
- permissible h2s contaminant concentration at a relative humidity 75:
- 10 ppm
- permissible so2 contaminant concentration at a relative humidity 75:
- 25 ppm
- pollution degree 5:
- 2 per IEC 61131-2
- power consumption 5 v system supply:
- 25 mA
- power consumption field supply module with no external load:
- 12 mA
- power consumption pmax:
- 0.45 W
- power loss pl:
- 0.45 W
- protection type:
- IP20
- rated surge voltage:
- 1 kV: Rated surge voltage between intrinsically safe and non-intrinsically safe circuits: 1.5 kV (EN 60079-11)
- reactances ex ia i:
- Lo = 100 mH: Co = 1000 F
- reactances ex ia iia:
- Lo = 100 mH: Co = 1000 F
- reactances ex ia iib:
- Lo = 100 mH: Co = 240 F
- reactances ex ia iic:
- Lo = 100 mH: Co = 13.5 F
- reactances note:
- Reactances without accounting for the concurrence of L and C
- relative humidity with condensation:
- Short-term condensation per Class 3K7/IEC EN 60721-3-3 and E-DIN 40046-721-3 (except for wind-driven precipitation, water and ice formation)
- relative humidity without condensation:
- 0.95
- resolution over entire range:
- 0.1 C, 0.1 , 0.0049 %
- safety relevant data circuit:
- Uo = 7.2 V: Io = 5.8 mA: Po = 10.5 mW: Linear characteristic curve
- sensor connection:
- 2 x (2-wire, 3-wire)
- sensor types:
- Pt100: Configurable: Pt200, Pt500, Pt1000, Ni100, Ni120, Ni1000: Resistors: 1.2 k, 5 k: Potentiometer setting 0 100 %: 1k2, 5k0
- shock resistance:
- Per IEC 60068-2-27 (15g/11 ms/half-sine/1,000 shocks: 25g/6 ms/1,000 shocks), EN 61373
- signal type:
- Resistance measurement || Potentiometer positions
- signal type configurable:
- Yes
- solid conductor:
- 0.25 2.5 mm / 24 14 AWG
- strip length:
- 8 9 mm / 0.31 0.35 inch
- supply voltage field:
- 24 VDC: (Ex i XTR power supply: UO = max. 26.8 V): via power jumper contacts (power supply via blade contact: transmission via spring contact)
- supply voltage system:
- 5 VDC: via data contacts
- surrounding air temperature operation:
- -40 70 C
- surrounding air temperature storage:
- -40 85 C
- temperature error max of the upper range value:
- 0.01 %/K
- temperature range:
- 200 +850 C (Pt), 60 +250 C (Ni), 80 +320 C (Ni120)
- total number of channels module:
- 2
- vibration resistance:
- Per IEC 60068-2-6 (acceleration: 5g), EN 60870-2-2, IEC 60721-3-1, -3
- weight:
- 90.600 g
- width: