- actuator connection:
- 2 x (2-wire, 3-wire)
- color:
- Dark gray
- conformity marking:
- CE
- connection technology inputs outputs:
- 6 x CAGE CLAMP
- connection type 1:
- Inputs/outputs
- country of origin sales organisation germany:
- DE
- current carrying capacity power jumper contacts:
- 0.416666666666667
- depth:
- 67.8 mm / 2.669 inch
- depth from upper edge of din rail:
- 60.6 mm / 2.386 inch
- derating:
- Derating (supply voltage): Surrounding air temperatures under laboratory conditions: (-25 +30 %): for -40 +55 C: 24 V (-25 +20 %): for +55 +70 C: 24 V (-25 +10 %): Lower limit in all temperature ranges: 27.5 % (
- diagnostics:
- Open circuit, overload and short circuit
- dielectric strength:
- 510 VAC/775 VDC: per EN 60870-2-1
- emc emission of interference:
- Per EN 61000-6-3, -4, EN 61131-2, EN 60255-26, marine applications, EN 60870-2-1, EN 61850-3, EN 50121-3-2, EN 50121-4, -5
- emc immunity to interference:
- Per EN 61000-6-1, -2: EN 61131-2: marine applications: EN 50121-3-2: EN 50121-4, -5: EN 60255-26: EN 60870-2-1: EN 61850-3: IEC 61000-6-5: IEEE 1613: VDEW: 1994
- exposure to pollutants:
- Per IEC 60068-2-42 and IEC 60068-2-43
- fine stranded conductor:
- 0.25 2.5 mm / 24 14 AWG
- fire load:
- 0.147 MJ
- height:
- 100 mm / 3.937 inch
- housing material:
- Polycarbonate: polyamide 6.6
- indicators:
- LED (A, E) green: Status DO 1, DO 2: LED (C, G) red: Error DO 1, DO 2
- input data width internal max:
- 2 bits
- interference free with safety function:
- Yes
- load type:
- Resistive, inductive, lamp load
- mounting position:
- Horizontal (standing/lying): vertical
- mounting type:
- DIN-35 rail
- number of digital outputs:
- 2
- number of incoming power jumper contacts:
- 2
- number of outgoing power jumper contacts:
- 2
- operating altitude:
- Without temperature derating: 0 2000 m: with temperature derating: 2000 5000 m (0.5 K/100 m): 5000 m (max.)
- output characteristic:
- High-side switching
- output current:
- Short-circuit-protected
- output current per channel:
- 0.0833333333333333
- output internal data width max:
- 2 bits
- packaging type:
- Box
- permissible h2s contaminant concentration at a relative humidity 75:
- 10 ppm
- permissible so2 contaminant concentration at a relative humidity 75:
- 25 ppm
- pollution degree 5:
- 2 per IEC 61131-2
- power consumption 5 v system supply:
- 14 mA
- power consumption field supply module with no external load:
- 7 mA
- protection type:
- IP20
- rated surge voltage:
- 1 kV
- relative humidity with condensation:
- Short-term condensation per Class 3K7/IEC EN 60721-3-3 and E-DIN 40046-721-3 (except for wind-driven precipitation, water and ice formation)
- relative humidity without condensation:
- 0.95
- shock resistance:
- Per IEC 60068-2-27 (15g/11 ms/half-sine/1,000 shocks: 25g/6 ms/1,000 shocks), EN 50155, EN 61373
- signal type:
- Voltage
- solid conductor:
- 0.25 2.5 mm / 24 14 AWG
- strip length:
- 8 9 mm / 0.31 0.35 inch
- supply voltage field:
- 24 VDC (-25 +30 %): via power jumper contacts (power supply via blade contact: transmission via spring contact): Derating must be observed!
- supply voltage system:
- 5 VDC: via data contacts
- surrounding air temperature operation:
- -40 70 C
- surrounding air temperature storage:
- -40 85 C
- switching frequency max:
- 1 kHz
- total number of channels module:
- 2
- vibration resistance:
- Per IEC 60068-2-6 (acceleration: 5g), EN 60870-2-2, IEC 60721-3-1, -3, EN 50155: EN 61373
- voltage signal type:
- 24 VDC
- weight:
- 46.948 g
- width:
- 12 mm / 0.472 inch