- achievable safety classes:
- 4 x Cat. 2/SIL 2 or 2 x Cat. 4/SIL 3
- actuator connection:
- 4 x (Fail-safe output with test pulse)
- color:
- Yellow
- configuration options:
- PROFIsafe address adjustable via DIP switch or engineering software
- conformity marking:
- CE
- connection technology inputs outputs:
- 16 x CAGE CLAMP
- connection type 1:
- Inputs/outputs
- country of origin sales organisation germany:
- DE
- current carrying capacity power jumper contacts:
- 0.416666666666667
- depth:
- 67.8 mm / 2.669 inch
- depth from upper edge of din rail:
- 60.6 mm / 2.386 inch
- emc emission of interference:
- Per EN 61000-6-4
- emc immunity to interference:
- Per EN 61000-6-2
- exposure to pollutants:
- Per IEC 60068-2-42 and IEC 60068-2-43
- fine stranded conductor:
- 0.08 2.5 mm / 28 14 AWG
- fire load:
- 2.309 MJ
- height:
- 100 mm / 3.937 inch
- housing material:
- Polycarbonate: polyamide 6.6
- indicators:
- LED (A-H) green: Status I1 I8: LED (I-K) red: internal, external error
- input characteristic:
- Clock sensitive
- input current per channel for signal 1 typ:
- 2.2 mA
- input response times min max:
- Ton (L->H) = 13 ms 71 ms: toff (H->L) = 13 ms 26 ms: plus 2 x local bus runtime: plus 2 x fieldbus runtime: plus PLC runtime
- isolation:
- 500 V system/field
- load reactances max:
- Capacitive 2 nF: inductive corresponding to DC 13
- load type of switching frequency:
- Resistive load
- mounting position:
- Horizontal (standing/lying): vertical
- mounting type:
- DIN-35 rail
- number of digital inputs:
- 4
- number of digital outputs:
- 4
- number of incoming power jumper contacts:
- 2
- number of outgoing power jumper contacts:
- 2
- operating altitude:
- 0 2000 m
- output circuit design:
- Power outputs
- output response times max:
- Ton (L->H) = 13 ms: toff (H->L) = 13 ms: plus 2 x local bus runtime: plus 2 x fieldbus runtime: plus PLC runtime
- packaging type:
- Box
- permissible h2s contaminant concentration at a relative humidity 75:
- 10 ppm
- permissible so2 contaminant concentration at a relative humidity 75:
- 25 ppm
- pollution degree 5:
- 2 per IEC 61131-2
- power consumption 5 v system supply:
- 55 mA
- proof test interval:
- 10 Years
- protection type:
- IP20
- relative humidity without condensation:
- 0.95
- sensor connection:
- 4 x (Fail-safe input with test pulse)
- shock resistance:
- 15g per IEC 60068-2-27
- signal type:
- Voltage
- solid conductor:
- 0.08 2.5 mm / 28 14 AWG
- strip length:
- 8 9 mm / 0.31 0.35 inch
- supply voltage field:
- 24 VDC (-15 +20 %): via power jumper contacts (power supply via blade contact: transmission via spring contact)
- supply voltage system:
- 5 VDC: via data contacts
- surrounding air temperature operation:
- 0 55 C
- surrounding air temperature storage:
- -40 85 C
- switching frequency max:
- 5 Hz: Resistive load
- switching frequency max 2:
- 0.1 Hz: Inductive load per IEC 947-5-1, DC 13
- switching frequency max 3:
- 5 Hz: Inductive load per IEC 947-5-1, DC 13: with recovery diodes
- total number of channels module:
- 8
- vibration resistance:
- Per IEC 60068-2-6
- voltage signal type:
- 24 VDC
- weight:
- 101.193 g
- width: