Polled I/O Message Connection || Strobed I/O Message Connection || Change of State || Cyclic Message Connection || UCMM using function blocks || DeviceNet master can be programmed
emc emission of interference:
Per EN 61000-6-4, marine applications
emc immunity to interference:
Per EN 61000-6-2, marine applications
exposure to pollutants:
Per IEC 60068-2-42 and IEC 60068-2-43
fine stranded conductor:
0.08 2.5 mm / 28 14 AWG
fire load:
2.587 MJ
height:
100 mm / 3.937 inch
housing material:
Polycarbonate: polyamide 6.6
indicators:
LED (OVERF) red: device error: LED (RUN) green: Device status: LED (BUS OFF) red: Network error : LED (CONNECT) green: Network status: LED (I/O, USR) red/green/orange: Local data bus status, status programmable by user: LED (A, B) green: System power
input and output fieldbus process image max:
1024 Byte/1024 Byte
input current typ at nominal load 24 v:
500 mA
input current via devicenet interface at 11 v:
120 mA
isolation:
500 V system/field
memory for fieldbus input variables max:
512 Byte
memory for fieldbus output variables max:
512 Byte
mounting position:
Any
mounting type:
DIN-35 rail
non volatile software memory:
8 kB
note:
Note: Configuration files required (EDS)!The EDS files can be downloaded for free at www.wago.com.
number of fieldbus nodes on master max:
64
number of i o points:
6000
number of modules per node max:
64
number of outgoing power jumper contacts:
3
operating altitude:
Without temperature derating: 0 2000 m: with temperature derating: 2000 5000 m (0.5 K/100 m): 5000 m (max.)
packaging type:
Box
permissible h2s contaminant concentration at a relative humidity 75:
10 ppm
permissible so2 contaminant concentration at a relative humidity 75:
25 ppm
pollution degree 5:
2 per IEC 61131-2
power consumption 5 v system supply:
350 mA
power supply efficiency typ at nominal load 24 v:
0.87
program memory:
128 kByte
programming environment:
WAGO-I/O-PRO V2.3 (based on CODESYS V2.3)
programming languages per iec 61131 3:
Instruction List (IL) || Ladder Diagram (LD) || Function Block Diagram (FBD), Continuous Function Chart (CFC) || Structured Text (ST) || Sequential Function Chart (SFC)