LED (DS, H11, H12, RUN, APP) red/green/orange: Device status, module status, network status, IEC RUN, application: LED (EC) red/blue/magenta: Error: LED (S, F) green: System supply, field supply
input and output internal process image max:
1000 Worte/1000 Worte
input and output modbus process image max:
e!RUNTIME: 1000 Worte/1000 Worte
internal memory flash:
4096 MB
isolation field system:
Min. 1000 VDC (1 min): per EN/UL 61010-2-201
main memory ram:
512 MB
marking:
Cl I, Div 2, Group A, B, C, D, T4
memory card slot:
Push-push mechanism
memory card type:
MicroSD up to 32 GB (all guaranteed properties only valid with WAGO's memory card)
mounting position:
Horizontal, typical for control cabinets (nominal mounting position): horizontal (floor mounting position): standing (vertical at bottom)
mounting type:
DIN-35 rail
non volatile hardware memory:
64 kB
non volatile software memory:
64 kB
number of modules per node max:
250
number of outgoing power jumper contacts:
2
operating altitude:
Without temperature derating: 0 2000 m: with temperature derating: 2000 3000 m (0.5 K/100 m)
operating system:
Real-time Linux (with RT-Preempt patch)
pollution degree 5:
2
power consumption system supply power supply at max local bus supply:
850 mA
power consumption system supply power supply without local bus supply:
180 mA
power loss pl:
4.8 W
power supply efficiency typ at nominal load 24 v:
0.95
program memory:
32 MB
programming environment:
e!COCKPIT (based on CODESYS V3)
programming languages per iec 61131 3:
Instruction List (IL) || Ladder Diagram (LD) || Function Block Diagram (FBD), Continuous Function Chart (CFC) || Structured Text (ST) || Sequential Function Chart (SFC)
protection type:
IP20
relative humidity without condensation:
0.95
solid conductor:
0.25 2.5 mm / 22 14 AWG
strip length:
8 9 mm / 0.31 0.35 inch
supply voltage field:
24 VDC, SELV (-25 +30 %): UF
supply voltage system:
24 VDC, SELV (-25 +30 %): US
surrounding air temperature operation:
-25 60 C (Horizontal, typical control cabinet installation: 25 +50 C, other mounting positions)
surrounding air temperature storage:
-40 85 C
temperature range of connecting cable per ul 61010 2 201 min:
85 C
temperature range of the connecting cable according to en 61010 2 201:
(Tsurrounding air + 25 K)
total current for system supply local bus max:
3000 mA
transmission medium communication fieldbus:
Twisted Pair S-UTP: 100 : Cat. 5: 100 m maximum cable length