- configuration options:
- DIP switch
- conformity marking:
- CE
- connection technology:
- Push-in CAGE CLAMP
- country of origin sales organisation germany:
- DE
- depth from upper edge of din rail:
- 97.8 mm / 3.85 inch
- emc emission of interference:
- EN 61000-6-3: EN 61326-1: EN 50121-3-2
- emc immunity to interference:
- EN 61000-6-2: EN 61326-1: EN 50121-3-2
- fine stranded conductor:
- 0.34 2.5 mm / 22 14 AWG
- fire load:
- 0.000 MJ
- height:
- 94 mm / 3.701 inch
- input current max:
- 50 mA
- input range resistor:
- 0 1 k: 0 4.5 k
- input signal type:
- Pt sensors || Resistor
- input voltage max:
- 30 V
- insulation type input analog output:
- Reinforced insulation
- line to neutral conductor voltage ac max:
- 150 V
- load impedance current output:
- See derating graphic
- measurement range temperature rtd:
- -200 850C
- measurement span rtd min:
- 50 K
- mounting type:
- DIN-35 rail
- operating altitude max:
- 2000 m
- output signal current:
- 4 20 mA: 20 4 mA
- output signal type:
- Current
- overvoltage category:
- II
- packaging type:
- Bag
- pollution degree:
- 2
- power supply type:
- Loop-powered (via output)
- relative humidity:
- 5 95 % (no condensation permissible)
- sensor connection:
- 2-wire: 3-wire: 4-wire (switchable)
- sensor power supply rtd max:
- ¤ 0.5 mA
- sensor types rtd:
- Pt100 || Pt200 || Pt500 || Pt1000
- solid conductor:
- 0.08 2.5 mm / 28 14 AWG
- standards specifications:
- EN 61010-1 || EN 61373
- step response typ:
- 1000 ms
- strip length:
- 9 10 mm / 0.35 0.39 inch
- supply voltage:
- DC 8 30 V (Power is derived from the output circuit.)
- surrounding air temperature operation:
- -25 70 C (at nominal current)
- surrounding air temperature storage:
- -40 85 C
- temperature coefficient:
- ¤ 0.02 %/K
- temperature range of connecting cable per ul 61010 2 201 min:
- 90 C
- temperature range of the connecting cable according to en 61010 2 201:
- (Tsurrounding air + 10 K)
- test voltage input analog output:
- 3 kVAC: 50 60 Hz: 1 min
- transmission error for the set measurement range:
- ¤ ((40 K/set measurement range [K]) + 0.1) %
- transmission error typ:
- ¤ 0.1 % at full measurement span
- weight:
- 38.940 g
- width:
- 6 mm / 0.236 inch