null

Lutze A1071804 lutze driveflex xlpe awg18/4c

(No reviews yet) Write a Review
SKU:
A1071804
Condition:
New
  • Lutze A1071804 lutze driveflex xlpe awg18/4c
  • Lutze A1071804 lutze driveflex xlpe awg18/4c

Description

Technical Data

Construction

Description
DRIVEFLEX?? XLPE (C) 1 TSP PVC
Number of conductors/cross-section
(4?????AWG18+1?????2?????AWG18)
Jacket material
PVC
Jacket color
black RAL 9005
Outer ?????
13,3 mm
Outer ?????
0,525 inch
Weight
156 Lbs/Mft
Cu-Index
66 Lbs/Mft

Element 1

Element construction
19/30
Conductor
  • AWG conductor
  • CU-wire tin-plated
Conductor category
fine wire
Conductor marking
  • black
  • with white number print
  • green/yellow
Conductor insulation
  • XLPE
  • XHHW-2
  • Wet/Dry

Element 2

Element construction
19/30
Conductor
  • AWG conductor
  • CU-wire tin-plated
Conductor marking
  • black
  • with white number print
Conductor insulation
  • XLPE
  • XHHW-2
  • Wet/Dry
Stranding
conductors stranded in pairs

overall construction

Drain wire
CU-wire tin-plated
Overall shield
  • Foil shield
  • Braid shield
  • Tinned copper wires
  • optical cover approx. 80%
Jacket characteristics
  • Oil resistant
  • Silicone-free

Technical data

Rated voltage UN
  • 600 V 90C UL TC-ER-JP
  • 1000 V Flexible VFD servo cable 90C
  • Cable, 1000 V 105C AWM
  • 1000 V WTTC
Temperature range fixed
-40 ???C ?? +90 ???C
Bending radius
6?????D

Element 1

Element construction
19/30

Element 2

Element construction
19/30

Approvals/Standards

Approvals
  • UL Flexible Motor Supply Cable
  • Flexible VFD Servo Cable
  • cULus
  • TC-ER
  • WTTC
  • UL DP-1
  • Meets NEC 336,392
  • Class I & II, Div. 2
  • 501, 502, 505
  • cUL TC
  • CIC FT4
  • UL 1277
  • cURus
UL style
AWM 20886
Conformity
  • CE
  • RoHS
  • REACH
Oil resistant according to
  • Oil Res I
  • Oil Res II

General

Note
CE These products are in conformity with the EU Low Voltage Directive 2014/35/EU

Shielded motor supply cable to connect power to 3-phase motors. VFD's and Servo Drives Cable design for harsh industrial environments and operating conditions with high noise levels Thermoset XLPE offering superior overload and short-circuit temperature Type XHHW-2 insulation offering smaller ODs for general VFD applications Compliant with NFPA 79 for wiring of industrial machinery TC-ER-JP for use with cable trays without conduit, which can reduce installation costs in industrial environments per NEC 336.10 (7) WTTC - wind turbine tray cable rating for use in wind power generation Dry, damp or wet conditions

View AllClose