Lutze A2204/003 driveflex 3 symmetrical ground

(No reviews yet) Write a Review
SKU:
A2204/003
Condition:
New
QN-QUOTE-REQUEST:
true
$81.25

Description

Technical Data

Construction

Description
DRIVEFLEX?? 3 SYMMETRICAL GROUNDS
Number of conductors/cross-section
(3??AWG4/0+3??AWG6)
Jacket material
PVC
Jacket color
black RAL 9005
Outer ??
47,8 mm
Outer ??
1,88 inch
Weight
3336 Lbs/Mft
Cu-Index
2461 Lbs/Mft

Element 1

Element construction
4/0/3C
Conductor construction
1638 strands
Conductor
  • AWG conductor
  • CU-wire tin-plated
Conductor category
fine wire
Conductor marking
  • black
  • with white number print
Conductor insulation
  • XLPE
  • XHHW-2

Element 2

Element construction
AWG6/3C
Conductor construction
206 strands
Conductor
  • AWG conductor
  • CU-wire tin-plated
Conductor category
fine wire
Conductor marking
green/yellow
Conductor insulation
  • XLPE
  • 3C XHHW-2 (Ground/PEs)

overall construction

Drain wire
CU-wire tin-plated
Overall shield
  • Foil shield
  • Aluminium laminate
  • Braid shield
  • Tinned copper wires
  • optical cover approx. 80%
Jacket characteristics
  • Oil resistant
  • Silicone-free

Technical data

Rated voltage UN
  • 600 V TC-ER
  • 1000 V Flexible VFD servo cable 90C
  • 1000 V WTTC
Temperature range fixed
-40 ???C ?? +90 ???C
Minimum bending radius fixed
7.5??D

Element 1

Element construction
4/0/3C

Element 2

Element construction
AWG6/3C

Approvals/Standards

Approvals
  • cULus
  • WTTC
  • TC-ER
  • cUL TC
  • CIC FT4
  • Class 1 Div. 2 per NEC
  • Art. 336, 392, 501
  • UL 1277
  • UL 2277
  • Wet/Dry
  • P-07-KA130021-MSHA
Conformity
  • CE
  • RoHS
  • REACH
Oil resistant according to
Oil Res II

General

Note
CE These products are in conformity with the EU Low Voltage Directive 2014/35/EU

Shielded VFD and Motor cable to connect power from drives to motors Three insulated symmetrical grounds design helps to reduce stray currents Cable design for harsh industrial environments and operating conditions with high noise levels 1 kV rated XLPE insulation with low capacitance, ideal for applications with high voltage spikes and long cable runs Compliant with NFPA 79 for wiring of industrial machinery TC-ER for use with cable trays without conduit, which can reduce material and labor costs WTTC ?? wind turbine tray cable rating for use in wind power generation Dry, damp or wet conditions

View AllClose