Schneider Electric ATS22C21Q soft starter for asynchronous motor, Altistart 22, control 230V, 230 to 440V, 55 to 110kW
Schneider Electric
$2,859.60
This Altistart 22 soft starter can feed 3-phase asynchronous motors in supply line or delta connection. It has a rating of 210A and 230V to 440V, a rated power up to 110kW (400V to 440V in supply line) and up to 160kW (400V to 440V in motor delta connection). It is designed for simple and complex machines such as centrifugal and piston pumps, fans, screw compressors and material handling equipment. Slim form factor improves versatility; allows mounting in frames of any kind of machines. It features an Integrated bypass, this reduces noise and decreases heat dissipation. Compatibility with SoMove software allows configurations and settings to be easily transferred, meaning spares can be quickly installed. It provides smooth starting for your machinery, avoiding mechanical stresses and extending their service life.
- Rohs Exemption Information:
- Yes
- Operating Altitude:
- <= 3280.84 ft (1000 m) without derating || > 3280.84...< 6561.68 ft (> 1000...< 2000 m) with current derating of 2.2 % per additional 100 m
- Minimum Switching Current:
- 100 mA 12 V DC relay outputs)
- Protection Type:
- phase failure line || thermal protection motor || thermal protection starter
- Phase:
- 3 phase
- Discrete Output Type:
- relay outputs R1 230 V running, alarm, trip, stopped, not stopped, starting, ready C/O || relay outputs R2 230 V running, alarm, trip, stopped, not stopped, starting, ready C/O
- Function Available:
- internal bypass
- Eu Rohs Directive:
- Pro-active compliance (Product out of EU RoHS legal scope)
- Noise Level:
- 56 dB
- Transmission Rate:
- 4800, 9600 or 19200 bps
- Product Or Component Type:
- soft starter
- Depth:
- 299 mm
- [Uc] Control Circuit Voltage:
- 230 V - 15...10 % 50/60 Hz
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- Range Of Product:
- Altistart 22
- Ambient Air Temperature For Storage:
- -25-70°C
- Component Name:
- ATS22
- Control Circuit Consumption:
- 20 W
- Motor Starter Type:
- soft starter
- Discrete Input Number:
- 3
- Discrete Input Voltage:
- 24 V <= 30 V
- Power Range:
- 55-100 kW 200-240 V 3 phase || 110-220 kW 380-440 V 3 phase
- Shock Resistance:
- 15 gn 11 ms IEC 60068-2-27
- Maximum Switching Current:
- 5 A 250 V AC resistive 1 relay outputs || 5 A 30 V DC resistive 1 relay outputs || 2 A 250 V AC inductive 0.4 20 ms relay outputs || 2 A 30 V DC inductive 7 ms relay outputs
- Weight:
- 33 kg
- Output Current:
- 0.4...1 Icl adjustable
- Relative Humidity:
- 0-95 % without condensation or dripping water IEC 60068-2-3
- Network Frequency:
- 45...66 Hz
- Electromagnetic Compatibility:
- conducted and radiated emissions level A IEC 60947-4-2 || damped oscillating waves level 3 IEC 61000-4-12 || electrostatic discharge level 3 IEC 61000-4-2 || immunity to electrical transients level 4 IEC 61000-4-4 || immunity to radiated radio-electr
- Net Weight:
- 33 kg
- Physical Interface:
- RS485 multidrop
- China Rohs Regulation:
- X
- Product Destination:
- asynchronous motors
- Pollution Degree:
- level 2 IEC 60664-1
- Icl Starter Rating:
- 210 A connection in the motor supply line for standard applications
- Factory Setting Current:
- 195 A
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Ip Degree Of Protection:
- IP00
- Type Of Start:
- start with torque control (current limited to 3.5 In)
- Power Dissipation In W:
- 117 W for standard applications
- Communication Data Link:
- serial
- [Us] Rated Supply Voltage:
- 230...440 V - 15...10 %
- Operating Position:
- vertical +/- 10 degree
- Country of Origin:
- China
- Standards:
- IEC 60947-4-2
- Ambient Air Temperature For Operation:
- -10-40°C without derating) || 40-60°C with current derating 2.2 % per°C)