Schneider Electric

Schneider Electric BCPMSCA1S 2 adapter boards - advanced - full power and energy on all circuits

(No reviews yet) Write a Review
SKU:
BCPMSCA1S
MPN:
BCPMSCA1S
Condition:
New
Mounting Support:
board
Product Name:
PowerLogic BCPMSC
Device Short Name:
BCPMSCA
Net Weight:
1.5 kg
Power Monitoring:
basic instrumentation
Ambient Air Temperature For Operation:
0-60°C
Country of Origin:
United States
Analogue Input Type:
current 0.333 V42 x || current 1 V
Mercury Free:
Yes
Weight:
1.5 kg
Measurement Accuracy:
branch current 2 % 0.25…2 A || branch current 1 % 2…100 A || mains current 3 % 1…100 % || mains current 3 % 2…100 % || voltage 1 % 90…277 V
Communication Port Protocol:
Modbus RTU
Network Frequency:
50 Hz || 60 Hz
California Proposition 65:
WARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Power Quality Analysis:
voltage sag and swell detection
Energy Management:
sub billing and cost allocation
Eu Rohs Directive:
Compliant with Exemptions
Standards:
EN 61010 || ANSI C12.1 || IEC 61010-1
[Us] Rated Supply Voltage:
90...277 V AC 50/60 Hz +/- 1 %
Product Or Component Type:
multi-circuit energy meter
Relative Humidity:
95-95 %
Sampling Rate:
256 samples/cycle
Product Certifications:
UL 508
Rohs Exemption Information:
Yes
Ambient Air Temperature For Storage:
-40-70°C
Device Application:
sub billing
China Rohs Regulation:
X
Operating Altitude:
9842.52 ft (3000 m)
Communication Port Support:
RS485
Update Time:
1.8 s
Provided Equipment:
2 x adapter board || 0 x current transformer
Type Of Measurement:
voltage || current || frequency || active power || power factor || active energy
Range:
PowerLogic
Variant:
advanced
Warranty:
18 months
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Mounting Mode:
clip-on
Communication Of Data:
high current alarm || high-high current alarm || low current alarm || over voltage alarm || low-low current alarm || under voltage alarm
Measurement Voltage:
90-277 V phase to neutral || 150-480 V phase to phase
$7,034.41

Description

This is an integrated solution for monitoring multi-circuits and mains by using a single meter. The meter is designed for retrofit and is used for critical power operations in data centres and energy management in buildings. It offers class 1 (1 %) power and energy system accuracy (including 50A, 100A or 200A split-core current transformers) on all branch channels. The BCPM allow the monitoring of both the branch circuits and mains values, incoming power and energy for a maximum of 42 circuits. All to provide information on the complete Power Distribution Unit. Full alarming capabilities ensure that potential issues are dealt with before they become problems. Communication enabled with a RS485 serial port and the Modbus protocol support, more communication options with the gateway H8951. The meter need to be powered by a 90V AC to 277V AC supply source. This version is for 42 circuits, but do not include branch current transformers nor ribbon. The device dimensions are 228mm in width, 146mm in height and weight 1.5 kilograms.