Schneider Electric

Schneider Electric BDA24030Y3 Circuit breaker, PowerPacT B, 30A, 2 pole, 480Y/277VAC, 18kA, I-Line, thermal magnetic, 80%, BA

(No reviews yet) Write a Review
SKU:
BDA24030Y3
MPN:
BDA24030Y3
Condition:
New
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
Device Application:
distribution
Wire Stripping Length:
20 mm
Awg Gauge:
AWG 14...AWG 2/0 aluminium/copper
Weight:
0.952 kg
Line Rated Current:
30-30 A
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 5000 m with derating
Suitability For Isolation:
yes IEC 60947-2
Height:
137 mm
Mercury Free:
Yes
Rohs Exemption Information:
Yes
Circularity Profile:
N/A
Device Short Name:
BD 030
Control Type:
toggle
Quantity Per Set:
set of 1
Utilisation Category:
category A
Local Signaling:
presence of auxiliary contacts flag green)
Pollution Degree:
3 IEC 60947-1
[Ics] Rated Service Breaking Capacity:
25 kA 220...240 V AC 50/60 Hz IEC 60947-2 || 14 kA 500...525 V AC 50/60 Hz IEC 60947-2 || 18 kA 380...415 V AC 50/60 Hz IEC 60947-2 || 18 kA 440 V AC 50/60 Hz IEC 60947-2
Environmental Disclosure:
ENVPEP2311047EN
Electrical Connection:
I-Line connection, line || lugs, load
Electrical Durability:
10000 cycles IEC 947-1 Annex K ed 5.2 440 V In
Number Of Slots:
1 auxiliary switch OF plug-in) || 1 voltage release MN or MX plug-in)
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Product Certifications:
UL || IEC || CCC || EAC || CSA || NOM
Phase Connection:
BA
Color:
Gray RAL 7016)
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Eu Rohs Directive:
Compliant with Exemptions
Poles Description:
2P
Range:
PowerPact
9 Mm Pitches:
6
Product Name:
PowerPact B
Mounting Mode:
I-Line
Trip Unit Technology:
thermal-magnetic
Standards:
GB 14048.2 || NEMA AB1 || UL 489 || EN/IEC 60947-5-1 || CSA C22.2 No 5 || NMX J-266 || EN/IEC 60947-2
Quality Labels:
CE
Breaking Capacity:
25 kA 208Y/120 V AC 50/60 Hz UL 489 || 25 kA 240 V AC 50/60 Hz UL 489 || 18 kA 480/277 V AC 50/60 Hz UL 489 || 18 kA 480 V AC 50/60 Hz UL 489 || 10 kA 600Y/347 V AC 50/60 Hz UL 489
Country of Origin:
United States
Continuous Current Rating:
0.8
Ik Degree Of Protection:
IK07 conforming to IEC 62262
[Ue] Rated Operational Voltage:
525 V AC 50/60 Hz UL 489
Height:
76.2 mm
Mounting Height:
76.2 mm
Ambient Air Temperature For Storage:
-50-85°C
Connection Pitch:
27 mm
Breaking Capacity Code:
D
$714.00

Description

PowerPacT B-Frame brings thermal-mechanical circuit protection in a compact size and offers a wide range of accessories, auxiliaries, and connection options. This PowerPacT B-Frame circuit breaker provides thermal magnetic circuit protection with a breaking capacity of 18kA at 480Y/277VAC. All PowerPacT B-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT B-Frame circuit breakers come in 1 to 4-pole unit mount construction and in 1 to 3-pole I-Line construction. I-Line circuit breakers come with a shrouded I-Line plug on jaw. This unit has I-Line terminations on the line side and mechanical lugs on the load side. This PowerPacT B, 30A, 2 pole, circuit breaker has a breaking capacity of 18kA at 480Y/277VAC. This circuit breaker has a continuous current rating of 80% with a BA phase connection. PowerPacT B circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
View AllClose