Schneider Electric

Schneider Electric BGA24020Y4 Circuit breaker, PowerPacT B, 20A, 2 pole, 480Y/277VAC, 35kA, I-Line, thermal magnetic, 80%, BC

(No reviews yet) Write a Review
SKU:
BGA24020Y4
MPN:
BGA24020Y4
Condition:
New
Environmental Disclosure:
ENVPEP2311047EN
Range:
PowerPact
Weight:
0.952 kg
Phase Connection:
BC
Line Rated Current:
20-20 A
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
Electrical Connection:
I-Line connection, line || lugs, load
Ambient Air Temperature For Storage:
-50-85°C
Suitability For Isolation:
yes IEC 60947-2
Length:
20 mm
9 Mm Pitches:
6
Mercury Free:
Yes
Rohs Exemption Information:
Yes
Circularity Profile:
N/A
Trip Unit Technology:
thermal-magnetic
[Ics] Rated Service Breaking Capacity:
65 kA 220...240 V AC 50/60 Hz IEC 60947-2 || 18 kA 500...525 V AC 50/60 Hz IEC 60947-2 || 35 kA 380...415 V AC 50/60 Hz IEC 60947-2 || 35 kA 440 V AC 50/60 Hz IEC 60947-2
Poles Description:
2P
Number Of Slots:
1 auxiliary switch OF plug-in) || 1 voltage release MN or MX plug-in)
Pollution Degree:
3 IEC 60947-1
Sustainable Offer Status:
Green Premium product
Color:
Gray RAL 7016)
Halogen Content Performance:
Halogen free product
Network Frequency:
50/60 Hz
Control Type:
toggle
Height:
76.2 mm
Breaking Capacity:
65 kA 208Y/120 V AC 50/60 Hz UL 489 || 65 kA 240 V AC 50/60 Hz UL 489 || 35 kA 480/277 V AC 50/60 Hz UL 489 || 35 kA 480 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 18 kA 600Y/347 V AC 50/60 Hz UL 489
Standards:
CSA C22.2 No 5 || NEMA AB1 || NMX J-266 || EN/IEC 60947-5-1 || EN/IEC 60947-2 || GB 14048.2 || UL 489
[Ui] Rated Insulation Voltage:
800 V IEC 60947-2
Depth:
89 mm
Connection Pitch:
27 mm
Ip Degree Of Protection:
front cover IP40 IEC 60529
Continuous Current Rating:
0.8
Local Signaling:
presence of auxiliary contacts flag green)
Mechanical Durability:
20000 cycles IEC 947-1 Annex K ed 5.2
Height:
137 mm
Circuit Breaker Application:
HACR rated
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Eu Rohs Directive:
Compliant with Exemptions
Device Application:
distribution
Tightening Torque:
3.6-4.4 N.m 2.5-6 mm² (AWG 14...AWG 10) || 5-6.2 N.m 10-70 mm² (AWG 8...AWG 2/0)
Breaking Capacity Code:
G
Wire Stripping Length:
20 mm
Electrical Durability:
10000 cycles IEC 947-1 Annex K ed 5.2 440 V In
Awg Gauge:
AWG 14...AWG 2/0 aluminium/copper
Ambient Air Temperature For Operation:
-25-70°C
Net Weight:
0.952 kg
Product Name:
PowerPact B
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
$964.00

Description

PowerPacT B-Frame brings thermal-mechanical circuit protection in a compact size and offers a wide range of accessories, auxiliaries, and connection options. This PowerPacT B-Frame circuit breaker provides thermal magnetic circuit protection with a breaking capacity of 35kA at 480Y/277VAC. All PowerPacT B-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT B-Frame circuit breakers come in 1 to 4-pole unit mount construction and in 1 to 3-pole I-Line construction. I-Line circuit breakers come with a shrouded I-Line plug on jaw. This unit has I-Line terminations on the line side and mechanical lugs on the load side. This PowerPacT B, 20A, 2 pole, circuit breaker has a breaking capacity of 35kA at 480Y/277VAC. This circuit breaker has a continuous current rating of 80% with a BC phase connection. PowerPacT B circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
View AllClose