Schneider Electric

Schneider Electric BGP36015 Circuit breaker, PowerPacT B, 15A, 3 pole, 600Y/347VAC, 18kA, lugs, thermal magnetic, 80%

(No reviews yet) Write a Review
SKU:
BGP36015
MPN:
BGP36015
Condition:
New
Electrical Connection:
Everlink lug, load || terminal nut, line
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 5000 m with derating
Country of Origin:
United States
Circuit Breaker Application:
HACR rated
Awg Gauge:
AWG 6...AWG 2/0 fine stranded aluminium/copper || AWG 14...AWG 3/0 rigid or stranded aluminium/copper
Length:
20 mm
Sustainable Offer Status:
Green Premium product
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Ik Degree Of Protection:
IK07 conforming to IEC 62262
Poles Description:
3P
9 Mm Pitches:
9
Network Frequency:
50/60 Hz
Rohs Exemption Information:
Yes
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Mechanical Durability:
20000 cycles IEC 947-1 Annex K ed 5.2
Environmental Disclosure:
ENVPEP1610005EN
Halogen Content Performance:
Halogen free product
Connection Pitch:
27 mm
Continuous Current Rating:
0.8
Ip Degree Of Protection:
front cover IP40 IEC 60529
Range:
PowerPact
Height:
137 mm
Eu Rohs Directive:
Compliant
Breaking Capacity:
65 kA 208Y/120 V AC 50/60 Hz UL 489 || 65 kA 240 V AC 50/60 Hz UL 489 || 35 kA 480/277 V AC 50/60 Hz UL 489 || 35 kA 480 V AC 50/60 Hz UL 489 || 18 kA 250 V DC UL 489 || 20 kA 600Y/347 V AC 50/60 Hz UL 489
[Ue] Rated Operational Voltage:
525 V AC 50/60 Hz UL 489
Net Weight:
1.074 kg
Electrical Durability:
10000 cycles IEC 947-1 Annex K ed 5.2 440 V In
Line Rated Current:
15-15 A
Quantity Per Set:
set of 1
Weight:
1.074 kg
Tightening Torque:
5-5 N.m 2.5-16 mm² (AWG 14...AWG 4) || 9-9 N.m 25-95 mm² (AWG 3...AWG 3/0)
Breaking Capacity Code:
G
Control Type:
toggle
Ambient Air Temperature For Operation:
-25-70°C
Device Short Name:
BG 015
Trip Unit Technology:
thermal-magnetic
Standards:
NEMA AB1 || GB 14048.2 || NMX J-266 || EN/IEC 60947-5-1 || EN/IEC 60947-2 || CSA C22.2 No 5 || UL 489
[Ics] Rated Service Breaking Capacity:
65 kA 220...240 V AC 50/60 Hz IEC 60947-2 || 18 kA 500...525 V AC 50/60 Hz IEC 60947-2 || 35 kA 380...415 V AC 50/60 Hz IEC 60947-2 || 35 kA 440 V AC 50/60 Hz IEC 60947-2
Ambient Air Temperature For Storage:
-50-85°C
Local Signaling:
presence of auxiliary contacts flag green)
Utilisation Category:
category A
Mercury Free:
Yes
Product Or Component Type:
circuit breaker
Color:
Gray RAL 7016)
[Ui] Rated Insulation Voltage:
800 V IEC 60947-2
Pollution Degree:
3 IEC 60947-1
Mounting Mode:
clip-on 35 x 15 mm symmetrical DIN rail) || by screws plate)
$1,344.00

Description

PowerPacT B-Frame brings thermal-mechanical circuit protection in a compact size and offers a wide range of accessories, auxiliaries, and connection options. This PowerPacT B-Frame circuit breaker provides thermal magnetic circuit protection with a breaking capacity of 18kA at 600Y/347VAC. All PowerPacT B-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT B-Frame circuit breakers come in 1 to 4-pole unit mount construction and in 1 to 3-pole I-Line construction. This circuit breaker's unit mount construction features traditional back pan mounting with screws or integrated DIN rail mounting for installation flexibility. This unit features EverLink lugs, a patented design to reduce loosening of cables over time, on the load side and terminal nuts on the line side. This PowerPacT B, 15A, 3 pole, circuit breaker has a breaking capacity of 18kA at 600Y/347VAC. This circuit breaker has a continuous current rating of 80%. PowerPacT B circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
View AllClose