Schneider Electric

Schneider Electric BMKC8020301 Modicon MC80, Controller, 8 DI, 12 DO, 4 AI

(No reviews yet) Write a Review
SKU:
BMKC8020301
MPN:
BMKC8020301
Condition:
New
Mercury Free:
Yes
Rohs Exemption Information:
Yes
Eu Rohs Directive:
Pro-active compliance (Product out of EU RoHS legal scope)
Range Of Product:
Modicon MC80
Product Compatibility:
BMXFTB20... terminal block analog input module || BMXFTB28... terminal block discrete I/O module
Product Or Component Type:
processor module
Discrete Input Voltage:
19...30 V DC
Discrete Output Voltage:
19...30 V DC
Integrated Connection Type:
USB port mini B USB
Function Available:
memory retention without battery
Discrete Input Number:
8 positive logic (sink)
Bus Length:
0-10 m serial link non isolated || 0-15 m serial link non isolated || 0-1000 m serial link isolated with external isolation tap || 0-20 m 1 Mbit/s CANopen || 0-2500 m 20 kbit/s CANopen || 0-100 m Ethernet
Communication Port Protocol:
1 non isolated serial link RJ45 RS485/RS232 0.3...19.2 kbit/s 247 || 1 CANopen SUB-D 9 20 kbit/s...1 Mbit/s 16 || 2 Ethernet RJ45 10/100 Mbit/s
Discrete Output Number:
12 positive
Marking:
CE
Protection Type:
overload protection output || short-circuit protection output
Communication Service:
read/write variables Modbus || diagnostics Modbus || send/receive character string character mode || Process Data Object (PDO) CANopen || Service Data Object (SDO) CANopen || FDR client Ethernet || SNMP Ethernet || RSTP support Ethernet
Discrete Input Type:
type 3
Realtime Clock:
with
Relative Humidity:
0-95 %
Current Consumption:
<= 700 mA
Country of Origin:
United States
Analogue Input Resolution:
16 bits
Ambient Air Temperature For Storage:
-40-85°C
Vibration Resistance:
3 gn
China Rohs Regulation:
X
Product Certifications:
RCM
Execution Time Per Instruction:
0.06µs Boolean || 0.08µs mixed
Ambient Air Temperature For Operation:
-25-70°C
Discrete Input Current:
2.4 mA
Analogue Input Number:
4
Analogue Input Type:
current - 20...20 mA || voltage - 10...10 V
California Proposition 65:
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Discrete Output Current:
2 A per output || 10 A per module
Nominal Read Cycle Time:
6.5 ms for 4 channels
Memory Description:
internal RAM 3840 kB || internal RAM 128 kB data || internal RAM 3590 kB program constants and symbols
Standards:
CSA C22.2 No 213 Class I Division 2 Group C || CSA C22.2 No 213 Class I Division 2 Group D || UL 508 || IEC 61131-2 || CSA C22.2 No 213 Class I Division 2 Group B || CSA C22.2 No 142 || CSA C22.2 No 213 Class I Division 2 Group A
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Port Ethernet:
10BASE-T/100BASE-TX
Product Specific Application:
thermo solar - parabolic through
[Us] Rated Supply Voltage:
24 V - 15...20 % DC
Fast Read Cycle Time:
1.3 ms + 1.3 ms x number of channels used
Isolation Voltage:
1500 V DC