Schneider Electric

Schneider Electric BMXDRA1605 discrete output module, Modicon X80, 16 NO relay outputs, 24 to 240V AC, 24 to 48V DC

(No reviews yet) Write a Review
SKU:
BMXDRA1605
MPN:
BMXDRA1605
Condition:
New
Minimum Switching Current:
1 mA 5 V DC
Ambient Air Temperature For Storage:
-40-85°C
Response Time On Output:
< 8 ms activation || < 10 ms deactivation
Typical Current Consumption:
100 mA 3.3 V DC || 95 mA 24 V DC
Discrete Output Voltage:
24...48 V 19...60 V DC || 24...240 V 19…264 V AC
Eu Rohs Directive:
Pro-active compliance (Product out of EU RoHS legal scope)
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Power Dissipation In W:
3 W
Product Or Component Type:
discrete output module
California Proposition 65:
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Output Overload Protection:
use 1 fast blow fuse per channel or group of channel
Discrete Output Number:
16 EN/IEC 61131-2
Output Overvoltage Protection:
use discharge diode on each output DC || use RC circuit on each output AC || use ZNO surge limiter on each output AC
Output Short-Circuit Protection:
use 1 fast blow fuse per channel or group of channel
Environmental Disclosure:
ENVPEP2311046EN
Vibration Resistance:
3 gn
Mtbf Reliability:
2100000 H
Warranty:
18 months
Relative Humidity:
5-95 % 55-55°C without condensation
Discrete Output Type:
relay
Circularity Profile:
ENVEOLI2311046EN
Net Weight:
0.15 kg
Dielectric Strength:
2000 V AC 50/60 Hz 1 min
Status Led:
1 LED (Green) RUN || 1 LED per channel (Green) channel diagnostic || 1 LED (Red) ERR || 1 LED (Red) I/O
Range Of Product:
Modicon X80
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Shock Resistance:
30 gn
Ambient Air Temperature For Operation:
0-60°C
Weight:
0.15 kg
China Rohs Regulation:
X
Mercury Free:
Yes
[Ith] Conventional Free Air Thermal Current:
0.0833333333333333
Operating Altitude:
0...6561.68 ft (0...2000 m) || 2000...5000 m with derating factor
Ip Degree Of Protection:
IP20
Insulation Resistance:
> 10 MOhm 500 V DC
Country of Origin:
United States
Electrical Durability:
AC-15 100000 cycles 240 VA 200 V 0.7 ) || AC-15 100000 cycles 120 VA 200 V 0.35 ) || AC-12 100000 cycles 200 VA 100 V || AC-12 100000 cycles 80 VA 48 V || AC-12 100000 cycles 50 VA 24 V || AC-15 100000 cycles 120 VA 100 V || AC-15 100000 cycles 120 V
$434.00

Description

This discrete output module is part of the Modicon X80 modules. It has 16 relay non protected outputs, 24V DC / 24V to 240V AC. This module is connected via 20-way removable terminal block. It occupies a single slot on the rack and it has a case which provides IP 20 protection of the electronics.
View AllClose