- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Eu Rohs Directive:
- Compliant
- [Ui] Rated Insulation Voltage:
- 690 V IEC 60947 || 750 V VDE 0110 group C || 690 V BS 5424 || 600 V CSA C22.2 No 14
- Pole Contact Composition:
- 2 NO + 2 NC
- Contactor Application:
- control circuit
- Heat Dissipation:
- 1.3-1.3 W
- Sustainable Offer Status:
- Green Premium product
- Irms Rated Making Capacity:
- 110 A IEC 60947
- [Ue] Rated Operational Voltage:
- <= 690 V <= 400 Hz
- Mounting Support:
- rail || plate
- Mechanical Robustness:
- vibrations contactor open2 Gn, 5...300 Hz IEC 60068-2-6 || vibrations contactor closed4 Gn, 5...300 Hz IEC 60068-2-6 || shocks contactor open10 Gn for 11 ms IEC 60068-2-27 || shocks contactor closed15 Gn for 11 ms IEC 60068-2-27
- Weight:
- 0.18 kg
- Toxic Heavy Metal Free:
- Yes
- Protective Treatment:
- TC IEC 60068
- Ambient Air Temperature For Operation:
- -25-50°C
- Reach Regulation:
- Free of Substances of Very High Concern above the threshold
- Associated Fuse Rating:
- 10 A gG conforming to IEC 60947 || 10 A gG conforming to VDE 0660
- [Uc] Control Circuit Voltage:
- 220...230 V AC 50/60 Hz
- Product Name:
- TeSys CAK
- Utilisation Category:
- AC-15 || DC-13
- Ambient Air Temperature For Storage:
- -50-80°C
- Standards:
- EN/IEC 60947-4-1 || GB/T 14048.4 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || JIS C8201-4-1
- China Rohs Regulation:
- Pro-active China RoHS declaration (out of China RoHS legal scope)
- Immunity To Microbreaks:
- 2 ms
- Net Weight:
- 0.18 kg
- Mercury Free:
- Yes
- Minimum Switching Current:
- 5 mA
- Mechanical Durability:
- 10 Mcycles
- Environmental Disclosure:
- ENVPEP1503003EN
- Depth:
- 57 mm
- Operating Altitude:
- 6561.68 ft (2000 m) without derating
- Insulation Resistance:
- > 10 MOhm
- Product Certifications:
- CB Scheme || CCC || UL || CSA || EAC || CE || UKCA
- Rohs Exemption Information:
- Yes
- Warranty:
- 18 months
- Reach Free Of Svhc:
- Yes
- Control Circuit Type:
- AC 50/60 Hz
- Ip Degree Of Protection:
- IP2X
- Minimum Switching Voltage:
- 17 V
- Control Circuit Voltage Limits:
- drop-out: 0.2...0.75 Uc (at <50°C) || operational: 0.8...1.15 Uc (at <50°C)
- Range:
- TeSys
- Device Short Name:
- CA2K
- Product Or Component Type:
- control relay
- Connections - Terminals:
- screw clamp terminals 1 1.5-4 mm²solid || screw clamp terminals 2 1.5-4 mm²solid || screw clamp terminals 1 0.75-4 mm²flexible with cable end || screw clamp terminals 2 0.75-4 mm²flexible without cable end || screw clamp terminals 1 0.34-1.5
- Operating Time:
- 10...20 ms coil de-energisation and NO opening || 10...20 ms coil energisation and NO closing || 15...25 ms coil de-energisation and NC closing || 5...15 ms coil energisation and NC opening