Schneider Electric

Schneider Electric CA3KN31GD Control relay, TeSys K, 3 NO + 1 NC, lt or eq to 690V, 125VDC standard coil

(No reviews yet) Write a Review
SKU:
CA3KN31GD
MPN:
CA3KN31GD
Condition:
New
[Ith] Conventional Free Air Thermal Current:
10 A (at 50°C)
Control Circuit Type:
DC standard
Non Overlap Distance:
0.5 mm
Weight:
0.225 kg
Pole Contact Composition:
3 NO + 1 NC
Associated Fuse Rating:
10 A gG conforming to IEC 60947 || 10 A gG conforming to VDE 0660
Protective Treatment:
TC IEC 60068
Control Circuit Voltage Limits:
operational: 0.8...1.15 Uc (at <50°C) || drop-out: 0.1...0.75 Uc (at <50°C)
Inrush Power In W:
3-3 W 20°C)
Operating Time:
10 ms coil de-energisation and NO opening || 30...40 ms coil energisation and NO closing || 15 ms coil de-energisation and NC closing || 25...35 ms coil energisation and NC opening
Toxic Heavy Metal Free:
Yes
Device Short Name:
CA3K
Ambient Air Temperature For Operation:
-25-50°C
Minimum Switching Voltage:
17 V
Product Or Component Type:
control relay
Utilisation Category:
DC-13 || AC-15
Range:
TeSys
Tightening Torque:
1.3 N.m screw clamp terminals flat Ø 6 mm || 1.3 N.m screw clamp terminals Philips No 2 6 mm || 1.3 N.m screw clamp terminals pozidriv No 2
[Ui] Rated Insulation Voltage:
690 V IEC 60947 || 750 V VDE 0110 group C || 690 V BS 5424 || 600 V CSA C22.2 No 14
Rohs Exemption Information:
Yes
Flame Retardance:
V1 conforming to UL 94 || requirement 2 conforming to NF F 16-101 || requirement 2 conforming to NF F 16-102
Reach Free Of Svhc:
Yes
Product Name:
TeSys CAK
Hold-In Power Consumption In W:
3-3 W 20°C
Net Weight:
0.225 kg
Ambient Air Temperature For Storage:
-50-80°C
Mechanical Robustness:
vibrations contactor open2 Gn, 5...300 Hz IEC 60068-2-6 || vibrations contactor closed4 Gn, 5...300 Hz IEC 60068-2-6 || shocks contactor open10 Gn for 11 ms IEC 60068-2-27 || shocks contactor closed15 Gn for 11 ms IEC 60068-2-27
Operating Altitude:
6561.68 ft (2000 m) without derating
Warranty:
18 months
Irms Rated Making Capacity:
110 A IEC 60947
Mechanical Durability:
20 Mcycles
Heat Dissipation:
3-3 W
[Uc] Control Circuit Voltage:
125 V DC
Eu Rohs Directive:
Compliant
Depth:
57 mm
Country of Origin:
Indonesia
Maximum Operating Rate:
10000 cyc/h
Sustainable Offer Status:
Green Premium product
Minimum Switching Current:
5 mA
Circularity Profile:
ENVEOLI1503003EN
Environmental Disclosure:
ENVPEP1503003EN
Immunity To Microbreaks:
2 ms
Mercury Free:
Yes
Insulation Resistance:
> 10 MOhm
[Ue] Rated Operational Voltage:
<= 690 V <= 400 Hz