Schneider Electric

Schneider Electric CAD323BL TeSys Deca control relay - 3 NO + 2 NC - <= 690 V - 24 V DC low consumption coil

(No reviews yet) Write a Review
SKU:
CAD323BL
MPN:
CAD323BL
Condition:
New
[Ith] Conventional Free Air Thermal Current:
10 A (at 60°C)
Width:
45 mm
Rohs Exemption Information:
Yes
Control Circuit Voltage Limits:
0.1...0.25 Uc -40-70°C drop-out DC || 0.7...1.25 Uc -40-60°C operational DC || 1...1.25 Uc 60-70°C operational DC
Product Certifications:
CB || CCC || UL || CSA || EAC || CE || UKCA
Time Constant:
40 ms
Net Weight:
0.58 kg
Operating Time:
65...88 ms coil energisation and NO closing || 14...25 ms coil de-energisation and NO opening || 57...77 ms coil energisation and NC opening || 28...42 ms coil de-energisation and NC closing
Eu Rohs Directive:
Compliant with Exemptions
Inrush Power In W:
2.4-2.4 W 20°C)
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
[Ue] Rated Operational Voltage:
<= 690 V AC 25...400 Hz
Control Circuit Type:
DC low consumption
Mechanical Durability:
30 Mcycles
Product Name:
TeSys CAD
Minimum Switching Voltage:
17 V
Product Or Component Type:
control relay
Standards:
EN/IEC 60947-5-1 || GB/T 14048.5 || UL 60947-5-1 || CSA C22.2 No 60947-5-1 || JIS C8201-5-1
Pole Contact Composition:
3 NO + 2 NC
Utilisation Category:
AC-14 || DC-13 || AC-15
Connections - Terminals:
spring terminals 1 1-2.5 mm²flexible without cable end || spring terminals 2 1-2.5 mm²flexible without cable end || spring terminals 1 1-2.5 mm²solid without cable end || spring terminals 2 1-2.5 mm²solid without cable end
Environmental Disclosure:
ENVPEP110230EN
Range:
TeSys || TeSys Deca
Minimum Switching Current:
5 mA
Warranty:
18 months
Ambient Air Temperature For Operation:
-40-60°C || 60-70°C with derating
Contactor Application:
control circuit
Mercury Free:
Yes
Hold-In Power Consumption In W:
2.4-2.4 W 20°C
Operating Altitude:
0...9842.52 ft (0...3000 m)
Ip Degree Of Protection:
IP2X VDE 0106
Mechanical Robustness:
shocks control relay open10 Gn for 11 ms IEC 60068-2-27 || shocks control relay closed15 Gn for 11 ms IEC 60068-2-27 || vibrations control relay open2 Gn, 5...300 Hz IEC 60068-2-6 || vibrations control relay closed4 Gn, 5...300 Hz IEC 60068-2-6
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Sustainable Offer Status:
Green Premium product
Mounting Support:
plate || rail
Country of Origin:
France
Non-Overlap Time:
1.5 ms on energisation between NC and NO contact || 1.5 ms on de-energisation between NC and NO contact
Circularity Profile:
ENVEOLI1102030EN
[Icw] Rated Short-Time Withstand Current:
100 A - 1 s || 120 A - 500 ms || 140 A - 100 ms
Ambient Air Temperature For Storage:
-60-80°C
[Uc] Control Circuit Voltage:
24 V DC
Irms Rated Making Capacity:
140 A AC IEC 60947-5-1 || 250 A DC IEC 60947-5-1
Protective Treatment:
TH IEC 60068
Depth:
93 mm
Weight:
0.58 kg
[Ui] Rated Insulation Voltage:
600 V UL || 600 V CSA || 690 V IEC 60947-5-1
$112.20

Description

TeSys D control relay, 5 contacts (3NO + 2NC), 10A/690V, for control of electromagnetic loads AC-15/DC-13. It provides a 24V DC control circuit, connection by spring terminals. For high operating rates until 180 cycles/min and ambient temperature -40/+60°C, it procures high reliability and durability. Compact (45mm width), for clipping on 35mm DIN rail or fixing by screw. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium product (RoHS/REACh).
View AllClose