Schneider Electric

Schneider Electric CAD323JD TeSys Deca control relay - 3 NO + 2 NC - <= 690 V - 12 V DC standard coil

(No reviews yet) Write a Review
SKU:
CAD323JD
MPN:
CAD323JD
Condition:
New
Sustainable Offer Status:
Green Premium product
[Uc] Control Circuit Voltage:
12 V DC
Hold-In Power Consumption In W:
5.4-5.4 W 20°C
Weight:
0.58 kg
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Associated Fuse Rating:
10 A gG conforming to IEC 60947-5-1
Minimum Switching Voltage:
17 V
Operating Altitude:
0...9842.52 ft (0...3000 m)
Rohs Exemption Information:
Yes
Insulation Resistance:
> 10 MOhm
[Ith] Conventional Free Air Thermal Current:
10 A (at 60°C)
Product Name:
TeSys CAD
Device Short Name:
CAD
Inrush Power In W:
5.4-5.4 W 20°C)
Pole Contact Composition:
3 NO + 2 NC
[Icw] Rated Short-Time Withstand Current:
100 A - 1 s || 120 A - 500 ms || 140 A - 100 ms
Irms Rated Making Capacity:
140 A AC IEC 60947-5-1 || 250 A DC IEC 60947-5-1
Product Or Component Type:
control relay
Protective Treatment:
TH IEC 60068
Non-Overlap Time:
1.5 ms on energisation between NC and NO contact || 1.5 ms on de-energisation between NC and NO contact
Contactor Application:
control circuit
Net Weight:
0.58 kg
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947
Circularity Profile:
ENVEOLI1501004
Mechanical Durability:
30 Mcycles
Connections - Terminals:
spring terminals 1 1-2.5 mm²flexible without cable end || spring terminals 2 1-2.5 mm²flexible without cable end || spring terminals 1 1-2.5 mm²solid without cable end || spring terminals 2 1-2.5 mm²solid without cable end
[Ue] Rated Operational Voltage:
<= 690 V AC 25...400 Hz
Environmental Disclosure:
ENVPEP1501004
Ambient Air Temperature For Storage:
-60-80°C
Ambient Air Temperature For Operation:
-40-60°C || 60-70°C with derating
Control Circuit Voltage Limits:
0.1...0.25 Uc -40-70°C drop-out DC || 0.7...1.25 Uc -40-60°C operational DC || 1...1.25 Uc 60-70°C operational DC
Mounting Support:
plate || rail
Mercury Free:
Yes
Country of Origin:
France
Standards:
EN/IEC 60947-5-1 || GB/T 14048.5 || UL 60947-5-1 || CSA C22.2 No 60947-5-1 || JIS C8201-5-1
[Ui] Rated Insulation Voltage:
600 V UL || 600 V CSA || 690 V IEC 60947-5-1
Maximum Operating Rate:
180 cyc/mn
Minimum Switching Current:
5 mA
Eu Rohs Directive:
Compliant with Exemptions
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Product Certifications:
CB || CCC || UL || CSA || EAC || CE || UKCA
Depth:
93 mm
Operating Time:
53...72 ms coil energisation and NO closing || 16...24 ms coil de-energisation and NO opening || 47...63 ms coil energisation and NC opening || 15...25 ms coil de-energisation and NC closing
Ip Degree Of Protection:
IP2X front face VDE 0106
Time Constant:
28 ms
Control Circuit Type:
DC standard
$168.30

Description

TeSys D control relay, 5 contacts (3NO + 2NC), 10A/690V, for control of electromagnetic loads AC-15/DC-13. It provides a 12V DC control circuit, connection by spring terminals. For high operating rates until 180 cycles/min and ambient temperature -40/+60°C, it procures high reliability and durability. Compact (45mm width), for clipping on 35mm DIN rail or fixing by screw. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium product (RoHS/REACh).
View AllClose