- Country of Origin:
- Indonesia
- Minimum Switching Current:
- 5 mA
- Inrush Power In Va:
- 70-70 VA 50 Hz (at 20°C)
- Ambient Air Temperature For Operation:
- -40-60°C || 60-70°C with derating
- Width:
- 45 mm
- Protective Treatment:
- TH IEC 60068
- [Uc] Control Circuit Voltage:
- 100 V AC 50/60 Hz
- Insulation Resistance:
- > 10 MOhm
- California Proposition 65:
- WARNING: Cancer - www.P65Warnings.ca.gov
- Product Certifications:
- CB || CCC || UL || CSA || EAC || CE || UKCA
- Eu Rohs Directive:
- Compliant with Exemptions
- Control Circuit Voltage Limits:
- 0.3...0.6 Uc -40-70°C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60°C operational AC 50 Hz || 0.85...1.1 Uc -40-60°C operational AC 60 Hz || 1...1.1 Uc 60-70°C operational AC 50/60 Hz
- [Ith] Conventional Free Air Thermal Current:
- 10 A (at 60°C)
- Weight:
- 0.58 kg
- Environmental Disclosure:
- ENVPEP1501004
- Ip Degree Of Protection:
- IP2X front face VDE 0106
- Mechanical Durability:
- 30 Mcycles
- Product Name:
- TeSys CAD
- [Ue] Rated Operational Voltage:
- <= 690 V AC 25...400 Hz
- [Uimp] Rated Impulse Withstand Voltage:
- 6 kV IEC 60947
- Net Weight:
- 0.58 kg
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Irms Rated Making Capacity:
- 140 A AC IEC 60947-5-1 || 250 A DC IEC 60947-5-1
- Circularity Profile:
- ENVEOLI1501004
- Depth:
- 84 mm
- Pole Contact Composition:
- 3 NO + 2 NC
- Mechanical Robustness:
- shocks control relay open10 Gn for 11 ms IEC 60068-2-27 || shocks control relay closed15 Gn for 11 ms IEC 60068-2-27 || vibrations control relay open2 Gn, 5...300 Hz IEC 60068-2-6 || vibrations control relay closed4 Gn, 5...300 Hz IEC 60068-2-6
- Operating Time:
- 12...22 ms coil energisation and NO closing || 4...12 ms coil de-energisation and NO opening || 4...19 ms coil energisation and NC opening || 6...17 ms coil de-energisation and NC closing
- Utilisation Category:
- AC-15 || AC-14 || DC-13
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Hold-In Power Consumption In Va:
- 8-8 VA 50 Hz (at 20°C)
- Device Short Name:
- CAD
- Sustainable Offer Status:
- Green Premium product
- Minimum Switching Voltage:
- 17 V
- Connections - Terminals:
- lugs-ring terminals 8 mm)
- Control Circuit Type:
- AC 50/60 Hz
- Warranty:
- 18 months
- Product Or Component Type:
- control relay
- Rohs Exemption Information:
- Yes
- Ambient Air Temperature For Storage:
- -60-80°C
- Operating Altitude:
- 0...9842.52 ft (0...3000 m)
- Associated Fuse Rating:
- 10 A gG conforming to IEC 60947-5-1
- Non-Overlap Time:
- 1.5 ms on energisation between NC and NO contact || 1.5 ms on de-energisation between NC and NO contact
- [Ui] Rated Insulation Voltage:
- 600 V UL || 600 V CSA || 690 V IEC 60947-5-1
- Contactor Application:
- control circuit
- [Icw] Rated Short-Time Withstand Current:
- 100 A - 1 s || 120 A - 500 ms || 140 A - 100 ms
- Maximum Operating Rate:
- 180 cyc/mn
- Range:
- TeSys || TeSys Deca