Schneider Electric

Schneider Electric CAD326V7 TeSys Deca control relay - 3 NO + 2 NC - <= 690 V - 400 V AC standard coil

(No reviews yet) Write a Review
SKU:
CAD326V7
MPN:
CAD326V7
Condition:
New
Minimum Switching Current:
5 mA
Sustainable Offer Status:
Green Premium product
[Icw] Rated Short-Time Withstand Current:
100 A - 1 s || 120 A - 500 ms || 140 A - 100 ms
Depth:
84 mm
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947
Ambient Air Temperature For Operation:
-40-60°C || 60-70°C with derating
Minimum Switching Voltage:
17 V
Mounting Support:
rail || plate
Circularity Profile:
ENVEOLI1501004
Contactor Application:
control circuit
[Uc] Control Circuit Voltage:
400 V AC 50/60 Hz
Height:
77 mm
Pole Contact Composition:
3 NO + 2 NC
Environmental Disclosure:
ENVPEP1501004
Ip Degree Of Protection:
IP2X front face VDE 0106
Utilisation Category:
DC-13 || AC-14 || AC-15
[Ith] Conventional Free Air Thermal Current:
10 A (at 60°C)
Weight:
0.58 kg
Country of Origin:
Indonesia
Irms Rated Making Capacity:
140 A AC IEC 60947-5-1 || 250 A DC IEC 60947-5-1
Control Circuit Voltage Limits:
0.3...0.6 Uc -40-70°C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60°C operational AC 50 Hz || 0.85...1.1 Uc -40-60°C operational AC 60 Hz || 1...1.1 Uc 60-70°C operational AC 50/60 Hz
Net Weight:
0.58 kg
Operating Altitude:
0...9842.52 ft (0...3000 m)
Standards:
EN/IEC 60947-5-1 || GB/T 14048.5 || UL 60947-5-1 || CSA C22.2 No 60947-5-1 || JIS C8201-5-1
Protective Treatment:
TH IEC 60068
Mechanical Robustness:
shocks control relay open10 Gn for 11 ms IEC 60068-2-27 || shocks control relay closed15 Gn for 11 ms IEC 60068-2-27 || vibrations control relay open2 Gn, 5...300 Hz IEC 60068-2-6 || vibrations control relay closed4 Gn, 5...300 Hz IEC 60068-2-6
[Ue] Rated Operational Voltage:
<= 690 V AC 25...400 Hz
[Ui] Rated Insulation Voltage:
600 V UL || 600 V CSA || 690 V IEC 60947-5-1
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Inrush Power In Va:
70-70 VA 50 Hz (at 20°C)
Eu Rohs Directive:
Compliant with Exemptions
Non-Overlap Time:
1.5 ms on energisation between NC and NO contact || 1.5 ms on de-energisation between NC and NO contact
Control Circuit Type:
AC 50/60 Hz
Hold-In Power Consumption In Va:
8-8 VA 50 Hz (at 20°C)
Product Or Component Type:
control relay
Range:
TeSys || TeSys Deca
Warranty:
18 months
Product Name:
TeSys CAD
Connections - Terminals:
lugs-ring terminals 8 mm)
Rohs Exemption Information:
Yes
Product Certifications:
CB || CCC || UL || CSA || EAC || CE || UKCA
Mercury Free:
Yes
Operating Time:
12...22 ms coil energisation and NO closing || 4...12 ms coil de-energisation and NO opening || 4...19 ms coil energisation and NC opening || 6...17 ms coil de-energisation and NC closing
Insulation Resistance:
> 10 MOhm
Mechanical Durability:
30 Mcycles
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Associated Fuse Rating:
10 A gG conforming to IEC 60947-5-1
$63.25

Description

TeSys D control relay, 5 contacts (3NO + 2NC), 10A/690V, for control of electromagnetic loads AC-15/DC-13. It provides a 400V 50/60Hz AC control circuit, connection by lugs. For high operating rates until 180 cycles/min and ambient temperature -40/+60°C, it procures high reliability and durability. Compact (45mm width), for clipping on 35mm DIN rail or fixing by screw. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium product (RoHS/REACh).
View AllClose