Schneider Electric

Schneider Electric CAD32F7 TeSys Deca control relay - 3 NO + 2 NC - <= 690 V - 110 V AC standard coil

(No reviews yet) Write a Review
SKU:
CAD32F7
MPN:
CAD32F7
Condition:
New
Pole Contact Composition:
3 NO + 2 NC
Utilisation Category:
AC-15 || AC-14 || DC-13
Inrush Power In Va:
70-70 VA 50 Hz (at 20°C)
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947
[Icw] Rated Short-Time Withstand Current:
100 A - 1 s || 120 A - 500 ms || 140 A - 100 ms
[Ue] Rated Operational Voltage:
<= 690 V AC 25...400 Hz
Depth:
84 mm
Irms Rated Making Capacity:
140 A AC IEC 60947-5-1 || 250 A DC IEC 60947-5-1
Contactor Application:
control circuit
Minimum Switching Voltage:
17 V
Range:
TeSys || TeSys Deca
Maximum Operating Rate:
180 cyc/mn
Mechanical Robustness:
shocks control relay open10 Gn for 11 ms IEC 60068-2-27 || shocks control relay closed15 Gn for 11 ms IEC 60068-2-27 || vibrations control relay open2 Gn, 5...300 Hz IEC 60068-2-6 || vibrations control relay closed4 Gn, 5...300 Hz IEC 60068-2-6
Control Circuit Voltage Limits:
0.3...0.6 Uc -40-70°C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60°C operational AC 50 Hz || 0.85...1.1 Uc -40-60°C operational AC 60 Hz || 1...1.1 Uc 60-70°C operational AC 50/60 Hz
Eu Rohs Directive:
Compliant with Exemptions
Control Circuit Type:
AC 50/60 Hz
Product Name:
TeSys CAD
Operating Altitude:
0...9842.52 ft (0...3000 m)
Standards:
EN/IEC 60947-5-1 || GB/T 14048.5 || UL 60947-5-1 || CSA C22.2 No 60947-5-1 || JIS C8201-5-1
Ambient Air Temperature For Operation:
-40-60°C || 60-70°C with derating
Width:
45 mm
Operating Time:
12...22 ms coil energisation and NO closing || 4...12 ms coil de-energisation and NO opening || 4...19 ms coil energisation and NC opening || 6...17 ms coil de-energisation and NC closing
Protective Treatment:
TH IEC 60068
Country of Origin:
France
Hold-In Power Consumption In Va:
8-8 VA 50 Hz (at 20°C)
Product Certifications:
CB || CCC || UL || CSA || EAC || CE || UKCA
Mechanical Durability:
30 Mcycles
[Ui] Rated Insulation Voltage:
600 V UL || 600 V CSA || 690 V IEC 60947-5-1
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Ip Degree Of Protection:
IP2X front face VDE 0106
Rohs Exemption Information:
Yes
Ambient Air Temperature For Storage:
-60-80°C
[Uc] Control Circuit Voltage:
110 V AC 50/60 Hz
[Ith] Conventional Free Air Thermal Current:
10 A (at 60°C)
Tightening Torque:
1.2 N.m screw clamp terminals Philips No 2 || 1.2 N.m screw clamp terminals flat Ø 6 mm || 1.2 N.m screw clamp terminals pozidriv No 2
Mercury Free:
Yes
Device Short Name:
CAD
Warranty:
18 months
Environmental Disclosure:
ENVPEP1501004
Connections - Terminals:
screw clamp terminals 1 1-4 mm²flexible without cable end || screw clamp terminals 2 1-4 mm²flexible without cable end || screw clamp terminals 1 1-4 mm²flexible with cable end || screw clamp terminals 2 1-2.5 mm²flexible with cable end || sc
Mounting Support:
rail || plate
Weight:
0.58 kg
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Insulation Resistance:
> 10 MOhm
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Sustainable Offer Status:
Green Premium product
Circularity Profile:
ENVEOLI1501004
$63.25

Description

TeSys D control relay, 5 contacts (3NO + 2NC), 10A/690V, for control of electromagnetic loads AC-15/DC-13. It provides a 110V 50/60Hz AC control circuit, connection by screw clamp terminals. For high operating rates until 180 cycles/min and ambient temperature -40/+60°C, it procures high reliability and durability. Compact (45mm width), for clipping on 35mm DIN rail or fixing by screw. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium product (RoHS/REACh).
View AllClose