Ambient Air Temperature For Storage:
-60-80°C
Warranty:
18 months
[Ith] Conventional Free Air Thermal Current:
10 A (at 60°C)
Contactor Application:
control circuit
Circularity Profile:
ENVEOLI1102030EN
Ip Degree Of Protection:
IP2X front face VDE 0106
Ambient Air Temperature For Operation:
-40-60°C || 60-70°C with derating
Mechanical Robustness:
shocks control relay open10 Gn for 11 ms IEC 60068-2-27 || shocks control relay closed15 Gn for 11 ms IEC 60068-2-27 || vibrations control relay open2 Gn, 5...300 Hz IEC 60068-2-6 || vibrations control relay closed4 Gn, 5...300 Hz IEC 60068-2-6
Net Weight:
0.58 kg
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Standards:
EN/IEC 60947-5-1 || GB/T 14048.5 || UL 60947-5-1 || CSA C22.2 No 60947-5-1 || JIS C8201-5-1
Eu Rohs Directive:
Compliant with Exemptions
Range:
TeSys || TeSys Deca
Irms Rated Making Capacity:
140 A AC IEC 60947-5-1 || 250 A DC IEC 60947-5-1
Product Name:
TeSys CAD
Minimum Switching Voltage:
17 V
Control Circuit Voltage Limits:
0.1...0.25 Uc -40-70°C drop-out DC || 0.7...1.25 Uc -40-60°C operational DC || 1...1.25 Uc 60-70°C operational DC
Depth:
93 mm
Hold-In Power Consumption In W:
5.4-5.4 W 20°C
Product Certifications:
CB || CCC || UL || CSA || EAC || CE || UKCA
Minimum Switching Current:
5 mA
Mechanical Durability:
30 Mcycles
[Uc] Control Circuit Voltage:
220 V DC
Product Or Component Type:
control relay
[Icw] Rated Short-Time Withstand Current:
100 A - 1 s || 120 A - 500 ms || 140 A - 100 ms
Operating Altitude:
0...9842.52 ft (0...3000 m)
Associated Fuse Rating:
10 A gG conforming to IEC 60947-5-1
Operating Time:
53...72 ms coil energisation and NO closing || 16...24 ms coil de-energisation and NO opening || 47...63 ms coil energisation and NC opening || 15...25 ms coil de-energisation and NC closing
Pole Contact Composition:
3 NO + 2 NC
[Ue] Rated Operational Voltage:
<= 690 V AC 25...400 Hz
Inrush Power In W:
5.4-5.4 W 20°C)
Sustainable Offer Status:
Green Premium product
[Ui] Rated Insulation Voltage:
600 V UL || 600 V CSA || 690 V IEC 60947-5-1
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Tightening Torque:
1.2 N.m screw clamp terminals Philips No 2 || 1.2 N.m screw clamp terminals flat Ø 6 mm || 1.2 N.m screw clamp terminals pozidriv No 2
Insulation Resistance:
> 10 MOhm
Weight:
0.58 kg
Mounting Support:
rail || plate
Country of Origin:
Indonesia
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Control Circuit Type:
DC standard
Rohs Exemption Information:
Yes
Time Constant:
28 ms
Utilisation Category:
AC-14 || AC-15 || DC-13
Device Short Name:
CAD
Protective Treatment:
TH IEC 60068
$112.20

Description

TeSys D control relay, 5 contacts (3NO + 2NC), 10A/690V, for control of electromagnetic loads AC-15/DC-13. It provides a 220V DC control circuit with no inrush consumption and equipped with a surge suppression device, connection by screw clamp terminals. For high operating rates until 180 cycles/min and ambient temperature -40/+60°C, it procures high reliability and durability. Compact (45mm width), for clipping on 35mm DIN rail or fixing by screw. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium product (RoHS/REACh).