- [Icw] Rated Short-Time Withstand Current:
- 100 A - 1 s || 120 A - 500 ms || 140 A - 100 ms
- Range:
- TeSys || TeSys Deca
- Protective Treatment:
- TH IEC 60068
- Environmental Disclosure:
- ENVPEP1501004
- Contactor Application:
- control circuit
- Mercury Free:
- Yes
- Country of Origin:
- Mexico
- Mechanical Robustness:
- shocks control relay open10 Gn for 11 ms IEC 60068-2-27 || shocks control relay closed15 Gn for 11 ms IEC 60068-2-27 || vibrations control relay open2 Gn, 5...300 Hz IEC 60068-2-6 || vibrations control relay closed4 Gn, 5...300 Hz IEC 60068-2-6
- Sustainable Offer Status:
- Green Premium product
- Maximum Operating Rate:
- 180 cyc/mn
- Insulation Resistance:
- > 10 MOhm
- Connections - Terminals:
- screw clamp terminals 1 1-4 mm²flexible without cable end || screw clamp terminals 2 1-4 mm²flexible without cable end || screw clamp terminals 1 1-4 mm²flexible with cable end || screw clamp terminals 2 1-2.5 mm²flexible with cable end || sc
- Control Circuit Type:
- AC 50/60 Hz
- Tightening Torque:
- 1.2 N.m screw clamp terminals Philips No 2 || 1.2 N.m screw clamp terminals flat Ø 6 mm || 1.2 N.m screw clamp terminals pozidriv No 2
- Operating Time:
- 12...22 ms coil energisation and NO closing || 4...12 ms coil de-energisation and NO opening || 4...19 ms coil energisation and NC opening || 6...17 ms coil de-energisation and NC closing
- Utilisation Category:
- DC-13 || AC-15 || AC-14
- Depth:
- 84 mm
- Ambient Air Temperature For Operation:
- -40-60°C || 60-70°C with derating
- Product Name:
- TeSys CAD
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- [Ue] Rated Operational Voltage:
- <= 690 V AC 25...400 Hz
- Associated Fuse Rating:
- 10 A gG conforming to IEC 60947-5-1
- Ambient Air Temperature For Storage:
- -60-80°C
- Warranty:
- 18 months
- Mounting Support:
- rail || plate
- Ip Degree Of Protection:
- IP2X front face VDE 0106
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Product Certifications:
- CB || CCC || UL || CSA || EAC || CE || UKCA
- Rohs Exemption Information:
- Yes
- Product Or Component Type:
- control relay
- Weight:
- 0.58 kg
- [Uimp] Rated Impulse Withstand Voltage:
- 6 kV IEC 60947
- Minimum Switching Voltage:
- 17 V
- Operating Altitude:
- 0...9842.52 ft (0...3000 m)
- Device Short Name:
- CAD
- [Ith] Conventional Free Air Thermal Current:
- 10 A (at 60°C)
- Non-Overlap Time:
- 1.5 ms on energisation between NC and NO contact || 1.5 ms on de-energisation between NC and NO contact
- Hold-In Power Consumption In Va:
- 8-8 VA 50 Hz (at 20°C)
- Mechanical Durability:
- 30 Mcycles
- Eu Rohs Directive:
- Compliant with Exemptions
- Minimum Switching Current:
- 5 mA
- Circularity Profile:
- ENVEOLI1501004
- [Ui] Rated Insulation Voltage:
- 600 V UL || 600 V CSA || 690 V IEC 60947-5-1
- Standards:
- EN/IEC 60947-5-1 || GB/T 14048.5 || UL 60947-5-1 || CSA C22.2 No 60947-5-1 || JIS C8201-5-1