- Product Certifications:
- CB Scheme || UL || CSA || EAC || CE || UKCA
- Control Circuit Type:
- AC 50...400 Hz || DC standard
- Eu Rohs Directive:
- Compliant with Exemptions
- Net Weight:
- 3.5 kg
- [Ue] Rated Operational Voltage:
- 1000 V AC 25...200 Hz
- Device Application:
- control
- Contactor Application:
- resistive load || motor control
- Maximum Operating Rate:
- 120 cyc/h 40°C
- Depth:
- 171 mm
- Pole Contact Composition:
- 3 NO
- [Ie] Rated Operational Current:
- 150 A (at <40°C) at <= 440 V AC AC-3 || 250 A (at <40°C) at <= 440 V AC AC-1 || 138 A (at <40°C) at <= 440 V AC AC-4
- Ambient Air Temperature For Storage:
- -60-80°C
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Average Coil Consumption:
- 1260 VA AC 50...400 Hz latching || 10 VA AC 50...400 Hz unlatching || 1260 VA DC latching || 10 VA DC unlatching
- Poles Description:
- 3P
- Operating Altitude:
- 9842.52 ft (3000 m) without derating
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- Protective Treatment:
- TC
- Average Impedance:
- 0.45 mOhm - Ith 250 A 50 Hz
- Utilisation Category:
- AC-3 || AC-1 || AC-4
- Weight:
- 3.5 kg
- [Ui] Rated Insulation Voltage:
- 1000 V IEC 60158-1 || 1000 V IEC 60947-4 || 1000 V BS 775 || 1500 V VDE 0110 group C
- Rated Breaking Capacity:
- 1500 A at 220...440 V || 1200 A at 500 V || 450 A at 1000 V || 1100 A at 660/690 V
- Operating Time:
- 35...40 ms latching || 50...100 ms unlatching
- Ambient Air Temperature For Operation:
- -15-70°C
- [Uc] Control Circuit Voltage:
- 110 V AC 50...400 Hz || 110 V DC
- Rohs Exemption Information:
- Yes
- Irms Rated Making Capacity:
- 1700 A
- Product Or Component Type:
- magnetic latching contactor
- Country of Origin:
- Czechia
- Range:
- TeSys
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Connections - Terminals:
- lugs-ring terminals 1 120-120 mm² || connector 1 120-120 mm² || bars 2 25 x 3 mm || power circuit bolted connection
- Motor Power Kw:
- 75 kW at 400 V AC 50/60 Hz (AC-4)
- Standards:
- EN/IEC 60947-1 || EN/IEC 60947-4-1 || JIS C8201-4-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Control Circuit Voltage Limits:
- latching: 0.85...1.1 Uc || unlatching: 0.85...1.1 Uc
- Mercury Free:
- Yes
- Warranty:
- 18 months
- [Icw] Rated Short-Time Withstand Current:
- 1200 A 40°C - 1 s || 1200 A 40°C - 5 s || 1200 A 40°C - 10 s || 700 A 40°C - 30 s || 600 A 40°C - 1 min || 450 A 40°C - 3 min || 350 A 40°C - 10 min
- Mechanical Durability:
- 1 Mcycles
- Associated Fuse Rating:
- 160 A aM at <= 440 V || 250 A BS88 at <= 440 V || 250 A gG at <= 440 V
- Tightening Torque:
- 18 N.m
- Device Short Name:
- CR1F
- Power Dissipation Per Pole:
- 6 W AC-3 || 18 W AC-1
- Product Name:
- TeSys F