Tightening Torque:
power circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || power circuit 1.7 N.m screw clamp terminals Philips No 2 || control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2
Pollution Degree:
3
Minimum Switching Voltage:
17 V for Signaling circuit
Control Circuit Type:
AC 50/60 Hz
Operating Altitude:
0...6561.68 ft (0...2000 m)
Hold-In Power Consumption In Va:
7.5-7.5 VA 60 Hz cos phi 0.3 (at 20°C) || 7-7 VA 50 Hz cos phi 0.3 (at 20°C)
Ip Degree Of Protection:
IP20 front face IEC 60529
Insulation Resistance:
> 10 MOhm for Signaling circuit
Pole Contact Composition:
3 NO
Auxiliary Contacts Type:
mechanically linked 1 NO IEC 60947-5-1
[Uc] Control Circuit Voltage:
240 V AC 50/60 Hz
Rohs Exemption Information:
Yes
Maximum Horse Power Rating:
0.5 hp at 115 V AC 50/60 Hz for 1 phase motors || 2 hp at 230/240 V AC 50/60 Hz for 1 phase motors || 3 hp at 200/208 V AC 50/60 Hz for 3 phase motors || 3 hp at 230/240 V AC 50/60 Hz for 3 phase motors || 7.5 hp at 460/480 V AC 50/60 Hz for 3 phase
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Product Certifications:
UL || CSA
Ambient Air Temperature For Operation:
-40-60°C
Minimum Switching Current:
5 mA for Signaling circuit
Maximum Operating Rate:
3600 cyc/h 60°C
Mounting Support:
rail || plate
Average Impedance:
2.5 mOhm - Ith 25 A 50 Hz for power circuit
[Ith] Conventional Free Air Thermal Current:
10 A (at 60°C) for Signaling circuit || 25 A (at 60°C) for power circuit
Toxic Heavy Metal Free:
Yes
Depth:
86 mm
Mechanical Robustness:
vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor open 10 Gn for 11 ms) || shocks contactor closed 15 Gn for 11 ms)
Product Name:
Easy TeSys DPE
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947
Country of Origin:
Indonesia
[Ui] Rated Insulation Voltage:
power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1
Control Circuit Voltage Limits:
drop-out: 0.3...0.6 Uc at 50/60 Hz (at <70°C) || operational: 0.8...1.1 Uc at 50 Hz (at <60°C) || operational: 0.85...1.1 Uc at 60 Hz (at <60°C) || operational: 1...1.1 Uc at 50/60 Hz (at <70°C)
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
Heat Dissipation:
2-3 W 50/60 Hz
Connections - Terminals:
power circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end || power circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end || power circuit: screw clamp terminals 1 1-4 mm² - cable
Utilisation Category:
AC-4 || AC-1 || AC-3
Ambient Air Temperature For Storage:
-60-80°C
Operating Time:
12...22 ms closing || 4...19 ms opening
Inrush Power In Va:
70-70 VA 60 Hz cos phi 0.75 (at 20°C) || 70-70 VA 50 Hz cos phi 0.75 (at 20°C)
Sustainable Offer Status:
Green Premium product
Overvoltage Category:
III
Poles Description:
3P
Contactor Application:
resistive load || motor control
Eu Rohs Directive:
Compliant
Range:
Easy TeSys
Mercury Free:
Yes
Power Dissipation Per Pole:
0.36 W AC-3 || 1.56 W AC-1
$42.50

Description

Easy TeSys DPE IEC contactor, 3 poles (3NO), for motor control applications up to 18A/690V AC-3 (7.5 HP@480V). It provides a 240V 50/60Hz AC coil, 1NO+1NC built-in auxiliary contacts (NC mirror certified), connection by screw clamp terminals. Compact (45mm width), DIN-rail mounting or screw fixing. Multi standards certified (IEC, UL, CSA), Green Premium compliant (RoHS/REACh).