Schneider Electric EGB36080 Miniature Circuit Breaker 600V 80A

(No reviews yet) Write a Review
SKU:
EGB36080
UPC:
785901578642
Condition:
New
Awg Gauge:
AWG 12...AWG 2/0 aluminium || AWG 14...AWG 2/0 copper
Local Signalling:
trip indicator
Eu Rohs Directive:
Pro-active compliance (Product out of EU RoHS legal scope)
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Warranty:
18 months
Rohs Exemption Information:
Yes
Mercury Free:
Yes
Device Short Name:
EGB
Protection Type:
short-circuit || overload
Number Of Poles:
3
Number Of Spaces Required:
3
Tightening Torque:
3.9-3.9 N.m 2.5-6 mm² (AWG 14...AWG 10) || 5.6-5.6 N.m 10-70 mm² (AWG 8...AWG 2/0)
Height:
5.66 in
Number Of Spaces:
3
Electrical Connection:
lugs aluminium
Net Weight:
4 lb(US)
Product Destination:
NF panelboard
Holding Current:
1000 A
Product Or Component Type:
circuit-breaker
Depth:
4.05 in
Width:
2.94 in
Mounting Mode:
bolt-on
Trip Unit Technology:
thermal-magnetic
Ambient Air Temperature For Operation:
40 °C
[Ue] Rated Operational Voltage:
600Y/347 V AC
Line Rated Current:
80 A
Trip Unit Rating:
2300-2300 A
Breaking Capacity:
18 kA 600Y/347 V AC
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Module Type:
E-Frame
Circuit Breaker Application:
HACR rated
Range Of Product:
125 A Frame EDB-EGB-EJB
Breaking Capacity Code:
G
Product Certifications:
cULus
$1,292.00

Description

E-Frame Breaker are Lighting Panelboard Circuit breakers that are proven effective and reliable which provide a wide variety or robust features that are use specifically in Square D NF Panelboards. This range of breaker is ideally designed to offer superior overload and short circuit protection. All E-Frame breakers have a thermal-magnetic trip unit as well as signal indicator that will indicate when a trip has occur. Mounting bolts are used to hold these breakers in place. This E-Frame breaker is 80A, 3 pole, and has an operating voltage of 600Y/347 VAC. It also provides a 65 kA max interrupt rating at 120 VAC. This device has a hold current of 1000A which is the maximum current the breaker can be held to ensure it will trip and a trip current of 2300A which is the current value when the breaker is guaranteed to trip. Many accessories are available for this breaker. This breaker was calibrated for 40 degrees C. HACR rated.
View AllClose