Schneider Electric

Schneider Electric EX225T3HF Transformer, dry type, DOE 2016, 225kVA, 3 phase, 480V delta primary, 208Y/120V secondary, 24J, 115C rise

(No reviews yet) Write a Review
SKU:
EX225T3HF
MPN:
EX225T3HF
Condition:
New
Ambient Air Temperature For Operation:
40-40°C
Rated Operational Power In Va:
225 kVA
Primary Voltage:
480 V delta
Device Application:
low voltage electrical distribution
Eu Rohs Directive:
Compliant
Degree Of Protection:
UL type 1 || UL type 2, with 7400DS25J || UL type 3R, with 7400WS25J
Material:
aluminium
Continuous Thermal Current Rating Factor:
1480 16.6 % || 1931 25 % || 4366 50 % || 8424 75 % || 14106 100 %
Rohs Exemption Information:
Yes
X/R Ratio:
2.47
Circularity Profile:
N/A
Range Of Product:
Square D
Electrical Connection:
4 Hole Nema Pad primary 11.1 mm || 6 Hole Nema Pad secondary 11.1 mm || 8 Hole Nema Pad sec - XO 11.1 mm
Type Of Cooling:
natural convection
[Ipk] Rated Peak Withstand Current:
13.9 kA
Transformer Type:
energy efficient
Phase:
3 phase
Toxic Heavy Metal Free:
Yes
Pvc Free:
Yes
Secondary Voltage:
208Y/120 V
California Proposition 65:
WARNING: This product can expose you to chemicals including: Phenyl Glycidyl Ether, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Environmental Disclosure:
ENVPEP1604028EN
Efficiency:
99.08 % at 35 % load factor , 75.0°C
Percentage Impedance Voltage:
0.00045
Weight:
657.71 kg
Percentage Reactance:
0.000418
Net Weight:
657.71 kg
Product Or Component Type:
transformer
Halogen Content Performance:
Halogen free plastic parts product
Number Of Tap-Offs:
2 2.5 % FCAN || 4 2.5 % FCBN
Temperature Rise:
115°C || 220°C insulated
[Uimp] Rated Impulse Withstand Voltage:
10 kV
Device Short Name:
DOE 2016
Box Number:
24J
Standards:
UL 1561 || CSA C22.2 No 47 || NEMA ST-20
Country of Origin:
United States
Mounting Support:
floor || floor, with 7400FMB
Network Frequency:
60 Hz
Average Ambient Air Temperature For Operation:
30°C
Depth:
832 mm
Reach Regulation:
Free of Substances of Very High Concern above the threshold
Sustainable Offer Status:
Green Premium product
Reach Free Of Svhc:
Yes
Tap Loss:
328 no load (core loss) || 3806 load loss (coil loss)
Noise Level:
6 dB NEMA ST-20 || 49 dB
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
$14,266.00

Description

EX three phase low voltage dry type distribution transformers from Square D comply with DOE energy conservation standards and Natural Resources Canada (NRCan) minimum energy efficiency levels. This transformer is a 225kVA, 480V primary (three wire), 208Y/120V secondary (four wire) with aluminum windings with a 220 insulation system design for 115 degree C temperature rise. This transformer’s DOE 2016 and NRCan efficiency is a minimum of 98.94% at 35% loading and 75°C temperature. Terminals are designed to accommodate wire ranges sized for 125% of the secondary nameplate current and 250% of the primary nameplate current. The terminals allow for NEMA two hole lugs and wiring bending radius to align with the wire ranges and to allow for side and bottom access. Units are natural air cooled with exhaust vents located on the front only, allowing the transformers to be mounted with rear clearance to obstructions of ½ inch. Units are shipped as Type 1 for indoor installation, field convertible to Type 2 via dripshield for indoor applications with dropping water or to Type 3R via weathershield for outdoor installation. The transformer's open bottom design limits the units to floor mounting. EX transformers have a low sound level, with a minimum of 3dB below NEMA Standard ST-20 requirements. Units are specifically designed to function with other Square D equipment; inrush is coordinated to meet identified breaker trip curves, and IZ levels allow for let through current to match AIR levels of panelboards. See product data sheets for these values.