Schneider Electric

Schneider Electric EX225T3HNLP Transformer, dry type, DOE 2016, 225kVA, 3 phase, 480V delta primary, 208Y/120V secondary, 25J, 150C rise, K13

(No reviews yet) Write a Review
SKU:
EX225T3HNLP
MPN:
EX225T3HNLP
Condition:
New
[Ipk] Rated Peak Withstand Current:
18.9 kA
Degree Of Protection:
UL type 1 || UL type 2, with 7400DS25J || UL type 3R, with 7400WS25J
Continuous Thermal Current Rating Factor:
1869 16.6 % || 2162 25 % || 3745 50 % || 6383 75 % || 10076 100 %
Transformer Type:
energy efficient
Rohs Exemption Information:
Yes
Net Weight:
895.84 kg
X/R Ratio:
2.82
Mounting Support:
floor || floor, with 7400FMB
Depth:
832 mm
Country of Origin:
Mexico
Weight:
895.84 kg
Device Application:
low voltage electrical distribution
Percentage Reactance:
0.00031
Halogen Content Performance:
Halogen free plastic parts product
Percentage Impedance Voltage:
0.033
Eu Rohs Directive:
Compliant
Reach Regulation:
Free of Substances of Very High Concern above the threshold
Sustainable Offer Status:
Green Premium product
Reach Free Of Svhc:
Yes
Network Frequency:
60 Hz
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
Secondary Voltage:
208Y/120 V
Phase:
3 phase
Rated Operational Power In Va:
225 kVA
Toxic Heavy Metal Free:
Yes
Device Short Name:
DOE 2016
Noise Level:
6 dB NEMA ST-20 || 49 dB
Efficiency:
99.09 % at 35 % load factor , 75.0°C
[Uimp] Rated Impulse Withstand Voltage:
10 kV
Electrical Connection:
4 Hole Nema Pad primary 11.1 mm || 6 Hole Nema Pad secondary 11.1 mm || 8 Hole Nema Pad sec - XO 11.1 mm
Pvc Free:
Yes
Box Number:
25J
Mercury Free:
Yes
Environmental Disclosure:
ENVPEP1604028EN
Average Ambient Air Temperature For Operation:
30°C
Ambient Air Temperature For Operation:
40-40°C
Tap Loss:
479 no load (core loss) || 2474 load loss (coil loss)
Material:
aluminium
Number Of Tap-Offs:
2 2.5 % FCAN || 4 2.5 % FCBN
Primary Voltage:
480 V delta
Temperature Rise:
150°C || 220°C insulated
Product Or Component Type:
transformer
California Proposition 65:
WARNING: This product can expose you to chemicals including: Phenyl glycidyl ether, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Circularity Profile:
N/A
Type Of Cooling:
natural convection
Range Of Product:
Square D
$19,982.00

Description

EX three phase low voltage dry type distribution transformers from Square D comply with DOE energy conservation standards and Natural Resources Canada (NRCan) minimum energy efficiency levels. This transformer is a 225kVA, 480V primary (three wire), 208Y/120V secondary (four wire) with aluminum windings with a 220 insulation system design for 150 degree C temperature rise, K-13 rated. This transformer’s DOE 2016 and NRCan efficiency is a minimum of 98.94% at 35% loading and 75°C temperature. Terminals are designed to accommodate wire ranges sized for 125% of the secondary nameplate current and 250% of the primary nameplate current. The terminals allow for NEMA two hole lugs and wiring bending radius to align with the wire ranges and to allow for side and bottom access. Units are natural air cooled with exhaust vents located on the front only, allowing the transformers to be mounted with rear clearance to obstructions of ½ inch. Units are shipped as Type 1 for indoor installation, field convertible to Type 2 via dripshield for indoor applications with dropping water or to Type 3R via weathershield for outdoor installation. The transformer's open bottom design limits the units to floor mounting. EX transformers have a low sound level, with a minimum of 3dB below NEMA Standard ST-20 requirements. Units are specifically designed to function with other Square D equipment; inrush is coordinated to meet identified breaker trip curves, and IZ levels allow for let through current to match AIR levels of panelboards. See product data sheets for these values.
View AllClose