Schneider Electric

Schneider Electric EXN15T3HNLP Transformer, dry type, DOE 2016, 15kVA, 3 phase, 480V delta primary, 208Y/120V secondary, 17M, 150C rise, K13

(No reviews yet) Write a Review
SKU:
EXN15T3HNLP
MPN:
EXN15T3HNLP
Condition:
New
[Uimp] Rated Impulse Withstand Voltage:
10 kV
Country of Origin:
Mexico
Standards:
UL 1561 || CSA C22.2 No 47 || NEMA ST-20
Circularity Profile:
N/A
California Proposition 65:
WARNING: This product can expose you to chemicals including: Phenyl Glycidyl Ether, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Percentage Reactance:
0.0279
[Ipk] Rated Peak Withstand Current:
0.92 kA
Material:
aluminium
Transformer Type:
energy efficient
Network Frequency:
60 Hz
Type Of Cooling:
natural convection
Device Short Name:
DOE 2016
Pvc Free:
Yes
Weight:
88.45 kg
Halogen Content Performance:
Halogen free plastic parts product
Ambient Air Temperature For Operation:
40-40°C
Reach Regulation:
Free of Substances of Very High Concern above the threshold
Depth:
538 mm
Percentage Impedance Voltage:
0.0451
Number Of Mounting Holes:
4 Ø: 13 mm
Electrical Connection:
2 Hole Nema Pad secondary 11.1 mm || 4 Hole Nema Pad sec - XO 11.1 mm || 2 Hole Nema Pad primary 11.1 mm
Rated Operational Power In Va:
15 kVA
Temperature Rise:
150°C || 220°C insulated
Net Weight:
88.45 kg
Secondary Voltage:
208Y/120 V
Range Of Product:
Square D
Primary Operational Current:
135.32-135.32 A 312.27 A 112.5 kVA
Number Of Tap-Offs:
2 2.5 % FCAN || 4 2.5 % FCBN
X/R Ratio:
1
Inrush Current:
239 A
Rohs Exemption Information:
Yes
Mounting Support:
floor || floor, with 7400FMB || ceiling, with 7400CMB17M || wall, with 7400WMB17M
Degree Of Protection:
UL type 2 || UL type 3R, with 7400WS22M
Primary Voltage:
480 V delta
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
Efficiency:
98.03 % at 35 % load factor , 75.0°C
Device Application:
low voltage electrical distribution
Continuous Thermal Current Rating Factor:
229 16.6 % || 293 25 % || 638 50 % || 1214 75 % || 2020 100 %
Eu Rohs Directive:
Compliant
Phase:
3 phase
Noise Level:
6 dB NEMA ST-20 || 39 dB
Mercury Free:
Yes
Reach Free Of Svhc:
Yes
Environmental Disclosure:
ENVPEP1604028EN
Tap Loss:
52 no load (core loss) || 540 load loss (coil loss)
Average Ambient Air Temperature For Operation:
30°C
$3,526.00

Description

EXN three phase low voltage dry type distribution transformers from Square D comply with DOE energy conservation standards and Natural Resources Canada (NRCan) minimum energy efficiency levels. This transformer is a 15kVA, 480V primary (three wire), 208Y/120V secondary (four wire) with aluminum windings with a 220 insulation system design for 150 degree C temperature rise, K-13 rated. This transformer’s DOE 2016 and NRCan efficiency is a minimum of 97.89% at 35% loading and 75°C temperature. Terminals are designed to accommodate wire ranges sized for 125% of the secondary nameplate current and 250% of the primary nameplate current. The terminals allow for NEMA two hole lugs and wiring bending radius to align with the wire ranges and to allow for side and bottom access. Units are natural air cooled with exhaust vents located on the front only, allowing the transformers to be mounted with rear clearance to obstructions of ½ inch. Units are shipped as Type 2 for indoor installation, field convertible to Type 3R via weathershield for outdoor installation. The transformers are floor mounted but field accessories are available for wall or trapeze (ceiling) mounting. EX transformers have a low sound level, with a minimum of 3dB below NEMA Standard ST-20 requirements. Units are specifically designed to function with other Square D equipment; inrush is coordinated to meet identified breaker trip curves, and IZ levels allow for let through current to match AIR levels of panelboards. See product data sheets for these values.
View AllClose