Schneider Electric

Schneider Electric EXN15T65HCU Transformer, dry type, DOE 2016, 15kVA, 3 phase, 600V delta primary, 208Y/120V secondary, 17M, 150C rise, Cu

(No reviews yet) Write a Review
SKU:
EXN15T65HCU
MPN:
EXN15T65HCU
Condition:
New
Rohs Exemption Information:
Yes
Efficiency:
98.16 % at 35 % load factor , 75.0°C
Noise Level:
6 dB NEMA ST-20 || 39 dB
Inrush Current:
221 A
Temperature Rise:
150°C || 220°C insulated
Continuous Thermal Current Rating Factor:
204 16.6 % || 264 25 % || 584 50 % || 1119 75 % || 1866 100 %
Number Of Mounting Holes:
4 Ø: 13 mm
Ambient Air Temperature For Operation:
40-40°C
Device Application:
low voltage electrical distribution
Reach Free Of Svhc:
Yes
Average Ambient Air Temperature For Operation:
30°C
Number Of Tap-Offs:
2 2.5 % FCAN || 4 2.5 % FCBN
Degree Of Protection:
UL type 2 || UL type 3R, with 7400WS22M
Product Or Component Type:
transformer
Tap Loss:
46 no load (core loss) || 501 load loss (coil loss)
[Ipk] Rated Peak Withstand Current:
1.10 kA
X/R Ratio:
0.56
Country of Origin:
United States
Transformer Type:
energy efficient
Range Of Product:
Square D
Percentage Reactance:
0.0185
Pvc Free:
Yes
Primary Voltage:
600 V delta
Phase:
3 phase
Material:
copper
Eu Rohs Directive:
Compliant
Net Weight:
106.14 kg
Type Of Cooling:
natural convection
Standards:
UL 1561 || CSA C22.2 No 47 || NEMA ST-20
Sustainable Offer Status:
Green Premium product
Reach Regulation:
Free of Substances of Very High Concern above the threshold
Electrical Connection:
2 Hole Nema Pad secondary 11.1 mm || 4 Hole Nema Pad sec - XO 11.1 mm || 2 Hole Nema Pad primary 11.1 mm
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
Secondary Voltage:
208Y/120 V
Rated Operational Power In Va:
15 kVA
Weight:
106.14 kg
Depth:
538 mm
Mounting Support:
floor || floor, with 7400FMB || ceiling, with 7400CMB17M || wall, with 7400WMB17M
Network Frequency:
60 Hz
Environmental Disclosure:
ENVPEP1604027EN
Device Short Name:
DOE 2016
[Uimp] Rated Impulse Withstand Voltage:
10 kV
Box Number:
17M
Percentage Impedance Voltage:
0.0378
California Proposition 65:
WARNING: This product can expose you to chemicals including: Phenyl Glycidyl Ether, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Mercury Free:
Yes
$5,339.00

Description

EXN three phase low voltage dry type distribution transformers from Square D comply with DOE energy conservation standards and Natural Resources Canada (NRCan) minimum energy efficiency levels. This transformer is a 15kVA, 600V primary (three wire), 208Y/120V secondary (four wire) with copper windings with a 220 insulation system design for 150 degree C temperature rise. This transformer’s DOE 2016 and NRCan efficiency is a minimum of 97.89% at 35% loading and 75°C temperature. Terminals are designed to accommodate wire ranges sized for 125% of the secondary nameplate current and 250% of the primary nameplate current. The terminals allow for NEMA two hole lugs and wiring bending radius to align with the wire ranges and to allow for side and bottom access. Units are natural air cooled with exhaust vents located on the front only, allowing the transformers to be mounted with rear clearance to obstructions of ½ inch. Units are shipped as Type 2 for indoor installation, field convertible to Type 3R via weathershield for outdoor installation. The transformers are floor mounted but field accessories are available for wall or trapeze (ceiling) mounting. EX transformers have a low sound level, with a minimum of 3dB below NEMA Standard ST-20 requirements. Units are specifically designed to function with other Square D equipment; inrush is coordinated to meet identified breaker trip curves, and IZ levels allow for let through current to match AIR levels of panelboards. See product data sheets for these values.
View AllClose