Transformer Type:
energy efficient
Rohs Exemption Information:
Yes
Weight:
146.96 kg
Device Short Name:
DOE 2016
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
[Uimp] Rated Impulse Withstand Voltage:
10 kV
Percentage Impedance Voltage:
0.037
Inrush Current:
399 A
Phase:
3 phase
Standards:
UL 1561 || CSA C22.2 No 47 || NEMA ST-20
Rated Operational Power In Va:
30 kVA
Percentage Reactance:
0.0161
Country of Origin:
United States
Box Number:
18M
Net Weight:
146.96 kg
Electrical Connection:
2 Hole Nema Pad primary 11.1 mm || 2 Hole Nema Pad secondary 11.1 mm || 4 Hole Nema Pad sec - XO 11.1 mm
[Ipk] Rated Peak Withstand Current:
2.25 kA
Number Of Mounting Holes:
4 Ø: 13 mm
Toxic Heavy Metal Free:
Yes
Depth:
627 mm
Tap Loss:
83 no load (core loss) || 1013 load loss (coil loss)
Material:
aluminium
Range Of Product:
Square D
Mercury Free:
Yes
Secondary Voltage:
208Y/120 V
California Proposition 65:
WARNING: This product can expose you to chemicals including: Phenyl Glycidyl Ether, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Eu Rohs Directive:
Compliant
Number Of Tap-Offs:
2 2.5 % FCAN || 4 2.5 % FCBN
Primary Operational Current:
28.87-28.87 A 83.27 A 30 kVA
Environmental Disclosure:
ENVPEP1604028EN
Ambient Air Temperature For Operation:
40-40°C
Noise Level:
6 dB NEMA ST-20 || 39 dB
Mounting Support:
floor || floor, with 7400FMB || ceiling, with 7400CMB18M19M20M || wall, with 7400WMB18M19M20M
Product Or Component Type:
transformer
Circularity Profile:
N/A
Reach Regulation:
Free of Substances of Very High Concern above the threshold
Continuous Thermal Current Rating Factor:
379 16.6 % || 499 25 % || 1147 50 % || 2227 75 % || 3740 100 %
Height:
719 mm
Degree Of Protection:
UL type 2 || UL type 3R, with 7400WS18M19M20M
Halogen Content Performance:
Halogen free plastic parts product
Sustainable Offer Status:
Green Premium product
X/R Ratio:
0.53
Primary Voltage:
600 V delta
Temperature Rise:
150°C || 220°C insulated
Device Application:
low voltage electrical distribution
Average Ambient Air Temperature For Operation:
30°C
Pvc Free:
Yes
Efficiency:
98.28 % at 35 % load factor , 75.0°C
$3,973.00

Description

EXN three phase low voltage dry type distribution transformers from Square D comply with DOE energy conservation standards and Natural Resources Canada (NRCan) minimum energy efficiency levels. This transformer is a 30kVA, 600V primary (three wire), 208Y/120V secondary (four wire) with aluminum windings with a 220 insulation system design for 150 degree C temperature rise. This transformer’s DOE 2016 and NRCan efficiency is a minimum of 98.23% at 35% loading and 75°C temperature. Terminals are designed to accommodate wire ranges sized for 125% of the secondary nameplate current and 250% of the primary nameplate current. The terminals allow for NEMA two hole lugs and wiring bending radius to align with the wire ranges and to allow for side and bottom access. Units are natural air cooled with exhaust vents located on the front only, allowing the transformers to be mounted with rear clearance to obstructions of ½ inch. Units are shipped as Type 2 for indoor installation, field convertible to Type 3R via weathershield for outdoor installation. The transformers are floor mounted but field accessories are available for wall or trapeze (ceiling) mounting. EX transformers have a low sound level, with a minimum of 3dB below NEMA Standard ST-20 requirements. Units are specifically designed to function with other Square D equipment; inrush is coordinated to meet identified breaker trip curves, and IZ levels allow for let through current to match AIR levels of panelboards. See product data sheets for these values.