Schneider Electric EXN75T3HCU Transformer, dry type, DOE 2016, 75kVA, 3 phase, 480V delta primary, 208Y/120V secondary, 20M, 150C rise, Cu

(No reviews yet) Write a Review
SKU:
EXN75T3HCU
MPN:
EXN75T3HCU
Condition:
New
Weight:
299.82 kg
California Proposition 65:
WARNING: This product can expose you to chemicals including: Phenyl Glycidyl Ether, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Ambient Air Temperature For Operation:
40-40°C
Reach Free Of Svhc:
Yes
Device Short Name:
DOE 2016
Range Of Product:
Square D
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
Mercury Free:
Yes
Percentage Reactance:
0.04
Secondary Voltage:
208Y/120 V
[Ipk] Rated Peak Withstand Current:
4.17 kA
Rated Operational Power In Va:
75 kVA
Primary Voltage:
480 V delta
Transformer Type:
energy efficient
Degree Of Protection:
UL type 2 || UL type 3R, with 7400WS18M19M20M
Device Application:
low voltage electrical distribution
Primary Operational Current:
90.21-90.21 A 208.18 A 75 kVA
Country of Origin:
Mexico
Network Frequency:
60 Hz
Box Number:
20M
Inrush Current:
733 A
Type Of Cooling:
natural convection
Circularity Profile:
N/A
Mounting Support:
floor || floor, with 7400FMB || ceiling, with 7400CMB18M19M20M || wall, with 7400WMB18M19M20M
Number Of Mounting Holes:
4 Ø: 13 mm
Percentage Impedance Voltage:
0.0499
Environmental Disclosure:
ENVPEP1604027EN
Reach Regulation:
Free of Substances of Very High Concern above the threshold
Average Ambient Air Temperature For Operation:
30°C
Standards:
UL 1561 || CSA C22.2 No 47 || NEMA ST-20
Depth:
697 mm
[Uimp] Rated Impulse Withstand Voltage:
10 kV
Material:
copper
X/R Ratio:
1.64
Efficiency:
98.66 % at 35 % load factor , 75.0°C
Product Or Component Type:
transformer
Noise Level:
44 dB || 6 dB NEMA ST-20
Number Of Tap-Offs:
2 2.5 % FCAN || 4 2.5 % FCBN
Sustainable Offer Status:
Green Premium product
Continuous Thermal Current Rating Factor:
645 16.6 % || 919 25 % || 2395 50 % || 4856 75 % || 8302 100 %
Tap Loss:
125 no load (core loss) || 2308 load loss (coil loss)
Electrical Connection:
2 Hole Nema Pad secondary 11.1 mm || 4 Hole Nema Pad sec - XO 11.1 mm || 4 Hole Nema Pad primary 11.1 mm
Eu Rohs Directive:
Compliant
Rohs Exemption Information:
Yes
Toxic Heavy Metal Free:
Yes
Net Weight:
299.82 kg
$8,896.00

Description

EXN three phase low voltage dry type distribution transformers from Square D comply with DOE energy conservation standards and Natural Resources Canada (NRCan) minimum energy efficiency levels. This transformer is a 75kVA, 480V primary (three wire), 208Y/120V secondary (four wire) with copper windings with a 220 insulation system design for 150 degree C temperature rise. This transformer’s DOE 2016 and NRCan efficiency is a minimum of 98.60% at 35% loading and 75°C temperature. Terminals are designed to accommodate wire ranges sized for 125% of the secondary nameplate current and 250% of the primary nameplate current. The terminals allow for NEMA two hole lugs and wiring bending radius to align with the wire ranges and to allow for side and bottom access. Units are natural air cooled with exhaust vents located on the front only, allowing the transformers to be mounted with rear clearance to obstructions of ½ inch. Units are shipped as Type 2 for indoor installation, field convertible to Type 3R via weathershield for outdoor installation. The transformers are floor mounted but field accessories are available for wall or trapeze (ceiling) mounting. EX transformers have a low sound level, with a minimum of 3dB below NEMA Standard ST-20 requirements. Units are specifically designed to function with other Square D equipment; inrush is coordinated to meet identified breaker trip curves, and IZ levels allow for let through current to match AIR levels of panelboards. See product data sheets for these values.
View AllClose