Schneider Electric

Schneider Electric EXN75T6H Transformer, dry type, DOE 2016, 75kVA, 3 phase, 480V delta primary, 240V delta secondary, 20M, 150C rise

(No reviews yet) Write a Review
SKU:
EXN75T6H
MPN:
EXN75T6H
Condition:
New
Weight:
239.95 kg
Rohs Exemption Information:
Yes
Network Frequency:
60 Hz
Device Short Name:
DOE 2016
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
[Uimp] Rated Impulse Withstand Voltage:
10 kV
Range Of Product:
Square D
Tap Loss:
144 no load (core loss) || 2126 load loss (coil loss)
California Proposition 65:
WARNING: This product can expose you to chemicals including: Phenyl Glycidyl Ether, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Primary Voltage:
480 V delta
Secondary Voltage:
240 V delta
Phase:
3 phase
Noise Level:
44 dB || 6 dB NEMA ST-20
Product Or Component Type:
transformer
Primary Operational Current:
90.21-90.21 A 180.42 A 75 kVA
Material:
aluminium
Degree Of Protection:
UL type 2 || UL type 3R, with 7400WS18M19M20M
Transformer Type:
energy efficient
Number Of Mounting Holes:
4 Ø: 13 mm
Ambient Air Temperature For Operation:
40-40°C
Reach Regulation:
Free of Substances of Very High Concern above the threshold
Eu Rohs Directive:
Compliant
Type Of Cooling:
natural convection
Toxic Heavy Metal Free:
Yes
Rated Operational Power In Va:
75 kVA
Device Application:
low voltage electrical distribution
[Ipk] Rated Peak Withstand Current:
3.55 kA
Mercury Free:
Yes
Mounting Support:
floor || floor, with 7400FMB || ceiling, with 7400CMB18M19M20M || wall, with 7400WMB18M19M20M
Depth:
697 mm
Average Ambient Air Temperature For Operation:
30°C
Continuous Thermal Current Rating Factor:
693 16.6 % || 945 25 % || 2305 50 % || 4572 75 % || 7746 100 %
Reach Free Of Svhc:
Yes
Percentage Impedance Voltage:
0.0508
Net Weight:
239.95 kg
Standards:
UL 1561 || CSA C22.2 No 47 || NEMA ST-20
Country of Origin:
United States
Electrical Connection:
4 Hole Nema Pad primary 11.1 mm
Efficiency:
98.66 % at 35 % load factor , 75.0°C
Box Number:
20M
Number Of Tap-Offs:
2 2.5 % FCAN || 4 2.5 % FCBN
Inrush Current:
777 A
Temperature Rise:
150°C || 220°C insulated
Percentage Reactance:
0.043
X/R Ratio:
1.83
$5,978.00

Description

EXN three phase low voltage dry type distribution transformers from Square D comply with DOE energy conservation standards and Natural Resources Canada (NRCan) minimum energy efficiency levels. This transformer is a 75kVA, 480V primary (three wire), 240V secondary (three wire) with aluminum windings with a 220 insulation system design for 150 degree C temperature rise. This transformer’s DOE 2016 and NRCan efficiency is a minimum of 98.60% at 35% loading and 75°C temperature. Terminals are designed to accommodate wire ranges sized for 125% of the secondary nameplate current and 250% of the primary nameplate current. The terminals allow for NEMA two hole lugs and wiring bending radius to align with the wire ranges and to allow for side and bottom access. Units are natural air cooled with exhaust vents located on the front only, allowing the transformers to be mounted with rear clearance to obstructions of ½ inch. Units are shipped as Type 2 for indoor installation, field convertible to Type 3R via weathershield for outdoor installation. The transformers are floor mounted but field accessories are available for wall or trapeze (ceiling) mounting. EX transformers have a low sound level, with a minimum of 3dB below NEMA Standard ST-20 requirements. Units are specifically designed to function with other Square D equipment; inrush is coordinated to meet identified breaker trip curves, and IZ levels allow for let through current to match AIR levels of panelboards. See product data sheets for these values.