Schneider Electric

Schneider Electric GB2CD16 TeSys GB2 thermal magnetic circuit protector, 1 P + N, 10 A, Id = 138 A

(No reviews yet) Write a Review
SKU:
GB2CD16
MPN:
GB2CD16
Condition:
New
Magnetic Tripping Current:
138-138 A
Circularity Profile:
N/A
Device Application:
control
Rohs Exemption Information:
Yes
California Proposition 65:
WARNING: Cancer - www.P65Warnings.ca.gov
Poles Description:
1P + N
Ip Degree Of Protection:
IP20 IEC 60529
Quantity Per Set:
set of 6
Sustainable Offer Status:
Green Premium product
Toxic Heavy Metal Free:
Yes
Protective Treatment:
TC
Fire Resistance:
960°C IEC 60695-2-1
Mechanical Robustness:
shocks 22 Gn for 20 ms IEC 60068-2-27 || vibrations 5 Gn, 5...110 Hz IEC 60068-2-6
Power Dissipation Per Pole:
2 W
Mounting Position:
horizontal || vertical
Tightening Torque:
1.2 N.m connector
Product Name:
TeSys GB2
Net Weight:
0.07 kg
Trip Unit Technology:
thermal-magnetic
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Reach Free Of Svhc:
Yes
Environmental Disclosure:
ENVPEP2306023
Mounting Mode:
by clips
Control Type:
toggle
Utilisation Category:
category A IEC 60947-2 || DC-12 IEC 60947-5-1 || DC-13 IEC 60947-5-1
Device Short Name:
GB2
Electrical Durability:
8000 cycles
Range:
TeSys
Network Type:
AC/DC
Reach Regulation:
Free of Substances of Very High Concern above the threshold
Depth:
67 mm
Standards:
EN/IEC 60947-1 || EN/IEC 60947-2 || CSA C22.2 No 235 || UL 1077
Weight:
0.07 kg
Warranty:
18 months
Ambient Air Temperature For Operation:
-20-60°C
[Uimp] Rated Impulse Withstand Voltage:
4 kV IEC 60947-2
Mercury Free:
Yes
Product Certifications:
UL || CSA
[Ics] Rated Service Short-Circuit Breaking Capacity:
75 % 110 V AC 50/60 Hz IEC 60947-2 || 75 % 230/240 V AC 50/60 Hz IEC 60947-2
Operating Altitude:
9842.52 ft (3000 m)
Connections - Terminals:
connector 1 0.75-6 mm²solid without cable end || connector 2 0.75-4 mm²solid without cable end || connector 1 0.75-4 mm²flexible with cable end || connector 2 0.75-2.5 mm²flexible with cable end
Country of Origin:
United States
Eu Rohs Directive:
Compliant
Breaking Capacity:
2 kA Icu 110 V AC 50/60 Hz IEC 60947-2 || 1.5 kA Icu 230/240 V AC 50/60 Hz IEC 60947-2 || 1.5 kA Icu 24 V DC IEC 60947-2
Mechanical Durability:
8000 cycles
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
$52.00

Description

TeSys GB circuit breaker, 2 poles (1P+N), 10A/250V IEC/277V UL, for the protection of industrial equipment control circuits. It provides thermal magnetic protection with a magnetic tripping level at 138A (13 In) and breaking capacity Icu 1.5kA@240V. It can also be used for protection of DC loads up to 10A/24V DC-13 with a breaking capacity Icu 1.5kA@24V. Compact device (30mm wide), mounting on 35mm DIN-rail, control by toggle lever (start-stop guaranteed for 8000 cycles). Sold in lots of 3 units. Multi standards certified (IEC, UL, CSA), Green Premium product (RoHS/REACh).
View AllClose