Schneider Electric

Schneider Electric GB2DB20 TeSys GB2 thermal magnetic circuit protector, 2 P, 12 A, Id = 165 A

(No reviews yet) Write a Review
SKU:
GB2DB20
MPN:
GB2DB20
Condition:
New
Utilisation Category:
category A IEC 60947-2 || DC-12 IEC 60947-5-1 || DC-13 IEC 60947-5-1
Reach Free Of Svhc:
Yes
Device Application:
control
Control Type:
toggle
Protective Treatment:
TC
Magnetic Tripping Current:
165-165 A
Mechanical Durability:
8000 cycles
[Ics] Rated Service Short-Circuit Breaking Capacity:
75 % 110 V AC 50/60 Hz IEC 60947-2 || 75 % 230/240 V AC 50/60 Hz IEC 60947-2 || 75 % 400/415 V AC 50/60 Hz IEC 60947-2
Electrical Durability:
8000 cycles
Eu Rohs Directive:
Compliant
9 Mm Pitches:
4
Reach Regulation:
Free of Substances of Very High Concern above the threshold
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Tightening Torque:
1.2 N.m connector
Poles Description:
2P
Mounting Support:
rail || plate
Ambient Air Temperature For Operation:
-20-60°C
Product Or Component Type:
circuit breaker
[Ue] Rated Operational Voltage:
415 V AC 50/60 Hz IEC 60947-2 || 48 V DC
Quantity Per Set:
set of 3
Range:
TeSys
Line Rated Current:
0
Circularity Profile:
N/A
Net Weight:
0.115 kg
Rohs Exemption Information:
Yes
Network Frequency:
50/60 Hz IEC 60947-2
Toxic Heavy Metal Free:
Yes
Fire Resistance:
960°C IEC 60695-2-1
Warranty:
18 months
Network Type:
AC/DC
Mechanical Robustness:
shocks 22 Gn for 20 ms IEC 60068-2-27 || vibrations 5 Gn, 5...110 Hz IEC 60068-2-6
Sustainable Offer Status:
Green Premium product
Ambient Air Temperature For Storage:
-40-80°C
Mounting Mode:
by clips
Device Short Name:
GB2
Connections - Terminals:
connector 1 0.75-6 mm²solid without cable end || connector 2 0.75-4 mm²solid without cable end || connector 1 0.75-4 mm²flexible with cable end || connector 2 0.75-2.5 mm²flexible with cable end
[Uimp] Rated Impulse Withstand Voltage:
4 kV IEC 60947-2
Power Dissipation Per Pole:
2 W
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
Operating Altitude:
9842.52 ft (3000 m)
Ip Degree Of Protection:
IP20 IEC 60529
Environmental Disclosure:
ENVPEP2306022
Country of Origin:
France
Standards:
EN/IEC 60947-1 || EN/IEC 60947-2
Breaking Capacity:
2 kA Icu 110 V AC 50/60 Hz IEC 60947-2 || 1.5 kA Icu 230/240 V AC 50/60 Hz IEC 60947-2 || 1.5 kA Icu 400/415 V AC 50/60 Hz IEC 60947-2 || 1.5 kA Icu 24 V DC IEC 60947-2
$139.50

Description

TeSys GB circuit breaker, 2 poles (2P), 12A/415V, for the protection of industrial equipment control circuits. It provides thermal magnetic protection with a magnetic tripping level at 165A (13 In) and breaking capacity Icu 1.5kA@415V. It can also be used for protection of DC loads up to 12A/24V DC-13 with a breaking capacity Icu 1.5kA@24V. Compact device (30mm wide), mounting on 35mm DIN-rail, control by toggle lever (start-stop guaranteed for 8000 cycles). Sold in lots of 3 units. It conforms to IEC 60947-1 and IEC 60947-2, Green Premium product (RoHS/REACh).
View AllClose