Schneider Electric

Schneider Electric GV2LE22 TeSys GV2 Manual Starter and Protector, magnetic circuit protector, toggle switch, 25 A, screw clamp terminals

(No reviews yet) Write a Review
SKU:
GV2LE22
MPN:
GV2LE22
Condition:
New
Country of Origin:
France
Net Weight:
0.33 kg
Control Type:
toggle
Color:
dark grey
Rated Duty:
continuous IEC 60947-4-1
Network Type:
AC
Suitability For Isolation:
yes IEC 60947-1§ 7-1-6
Depth:
78.5 mm
Mercury Free:
Yes
Power Dissipation Per Pole:
1.8 W
Ambient Air Temperature For Operation:
-20-60°C
Product Name:
TeSys GV2
Motor Power Kw:
9-9 kW 400/415 V AC 50/60 Hz || 11-11 kW 400/415 V AC 50/60 Hz || 11-11 kW 500 V AC 50/60 Hz || 15-15 kW 500 V AC 50/60 Hz || 18.5-18.5 kW 690 V AC 50/60 Hz
[Ue] Rated Operational Voltage:
690 V AC 50/60 Hz IEC 60947-2
Magnetic Tripping Current:
327-327 A
Breaking Capacity:
50 kA Icu 230/240 V AC 50/60 Hz IEC 60947-2 || 15 kA Icu 400/415 V AC 50/60 Hz IEC 60947-2 || 6 kA Icu 440 V AC 50/60 Hz IEC 60947-2 || 4 kA Icu 500 V AC 50/60 Hz IEC 60947-2 || 3 kA Icu 690 V AC 50/60 Hz IEC 60947-2
Poles Description:
3P
Environmental Disclosure:
ENVPEP121004
Electrical Durability:
100000 cycles AC-3 415 V In || 100000 cycles AC-3e 415 V In
Operating Altitude:
6561.68 ft (2000 m)
Network Frequency:
50/60 Hz IEC 60947-2
[Ith] Conventional Free Air Thermal Current:
25 A IEC 60947-4-1
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Device Short Name:
GV2LE
[Ics] Rated Service Short-Circuit Breaking Capacity:
100 % 230/240 V AC 50/60 Hz IEC 60947-2 || 40 % 400/415 V AC 50/60 Hz IEC 60947-2 || 50 % 440 V AC 50/60 Hz IEC 60947-2 || 75 % 500 V AC 50/60 Hz IEC 60947-2 || 75 % 690 V AC 50/60 Hz IEC 60947-2
Warranty:
18 months
Device Application:
motor protection
Range:
TeSys Deca
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Ip Degree Of Protection:
IP20 IEC 60529
Circularity Profile:
ENVEOLI121004
Fire Resistance:
960°C IEC 60695-2-11
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947-2
Tightening Torque:
1.7 N.m screw clamp terminal
Mechanical Robustness:
shocks 30 Gn for 11 ms || vibrations 5 Gn, 5...150 Hz
Product Or Component Type:
motor circuit breaker
Utilisation Category:
category A IEC 60947-2 || AC-3 IEC 60947-4-1 || AC-3e IEC 60947-4-1
Rohs Exemption Information:
Yes
Fixing Mode:
35 mm symmetrical DIN rail clipped || panel screwed with adaptor plate)
[Ui] Rated Insulation Voltage:
690 V AC 50/60 Hz IEC 60947-2
Product Certifications:
CCC || UL || EAC || BV || RINA || UKCA
Eu Rohs Directive:
Compliant with Exemptions
Weight:
0.33 kg
Trip Unit Technology:
magnetic
Line Rated Current:
25 A
Ambient Air Temperature For Storage:
-40-80°C
$378.00

Description

TeSys GV motor circuit breaker, 3 poles (3P), 25A/690V, for 3-phase motor applications 11kW@400V. It provides a magnetic protection with a tripping level at 13xIn, high breaking capacity Icu 15kA@400V. Connection by screw clamp terminals. Start-stop control by toggle guaranteed for 100 000 cycles AC-3. To complete motor protection, use in association with a thermal overload relay LRD22 (to be ordered separately). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).
View AllClose