Schneider Electric

Schneider Electric GV4P25B Motor circuit breaker, TeSys GV4, 3P, 25A, Icu 25kA, thermal magnetic, Everlink terminals

(No reviews yet) Write a Review
SKU:
GV4P25B
MPN:
GV4P25B
Condition:
New
Environmental Disclosure:
ENVPEP1704004EN
Pollution Degree:
3
Depth:
165 mm
Power Dissipation Per Pole:
4.6 W
Sustainable Offer Status:
Green Premium product
Halogen Content Performance:
Halogen free plastic parts product
Circularity Profile:
ENVEOLI1704004EN
Operating Position:
any position
Magnetic Tripping Current:
425-425 A
Device Short Name:
GV4P
Trip Unit Technology:
electronic || thermal-magnetic
Device Application:
motor protection
Breaking Capacity:
50 kA Icu 220...240 V AC 50/60 Hz IEC 60947-2 || 25 kA Icu 380...415 V AC 50/60 Hz IEC 60947-2 || 20 kA Icu 440 V AC 50/60 Hz IEC 60947-2 || 10 kA Icu 500 V AC 50/60 Hz IEC 60947-2 || 35 kA 208Y/120 V AC 50/60 Hz UL 60947 || 35 kA 240 V AC 50/60 Hz U
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Line Rated Current:
25 A
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Suitability For Isolation:
yes IEC 60947-1
Poles Description:
3P
Standards:
EN/IEC 60947-4-1 || EN/IEC 60947-2 || UL 60947-4-1 || CSA C22.2 No 60947-4-1
Country of Origin:
Poland
Connections - Terminals:
EverLink BTR screw connectors top) 1 1.5-70 mm² - solid || EverLink BTR screw connectors top) 1 1.5-50 mm² - flexible || EverLink BTR screw connectors bottom) 1 2.5-95 mm² - solid || EverLink BTR screw connectors bottom) 1 2.5-70 mm² - flexible
Maximum Operating Rate:
25 cyc/h
Range Of Product:
TeSys GV4
Product Certifications:
IEC || UL || CSA || CCC || EAC || ATEX || EU-RO MR
Fire Resistance:
960°C IEC 60695-2-11
Mechanical Robustness:
vibrations +/- 1 mm 2...13.2 Hz IEC 60068-2-6 || vibrations 0.7 gn 13.2...100 Hz IEC 60068-2-6 || shocks 15 gn 11 ms IEC 60068-2-27
Warranty:
18 months
Product Name:
TeSys GV4 || TeSys Deca
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Net Weight:
1.6 kg
Electrical Durability:
40000 cycles AC-3 440 V In/2 || 20000 cycles AC-3 440 V In
Color:
Gray RAL 7016)
Control Type:
rotary handle
[Ui] Rated Insulation Voltage:
800 V AC 50/60 Hz IEC 60947-2
Weight:
1.6 kg
Rohs Exemption Information:
Yes
Climatic Withstand:
IACS E10
Width:
81 mm
Motor Power Kw:
7.5-7.5 kW 660...690 V AC 50/60 Hz || 5.5-5.5 kW 400...415 V AC 50/60 Hz || 7.5-7.5 kW 500 V AC 50/60 Hz || 9-9 kW 660...690 V AC 50/60 Hz || 11-11 kW 660...690 V AC 50/60 Hz || 7.5-7.5 kW 400...415 V AC 50/60 Hz || 9-9 kW 400...415 V AC 50/60 Hz ||
Pvc Free:
Yes
[Ith] Conventional Free Air Thermal Current:
115 A IEC 60947-4-1
Mercury Free:
Yes
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Ik Degree Of Protection:
IK07 IEC 62262
Rated Duty:
continuous IEC 60947-4-1
Ambient Air Temperature For Operation:
-25-70°C
Eu Rohs Directive:
Compliant with Exemptions
Phase Failure Sensitivity:
yes IEC 60947-4-1
$967.50

Description

TeSys GV motor circuit breaker, 3 poles (3P), 25A/690V, for protection of 3-phase motors 5.5-11kW@400V. It provides thermal magnetic protection and additional motor protection functions, breaking capacity Icu 25kA@400V, start-stop control by rotary handle, connection by Everlink BTR screw terminals. Thermal protection adjustable by dials with a setting current Ir in range 10-25A and a selectable tripping class 10 or 20, magnetic protection at 17 In. Additional protections have fixed pick-up and include short time delay protection Isd at 13 Ir, phase unbalance and loss protection, ground fault protection. It makes internal locations available for additional auxiliary contact blocks (OF, SD), and voltage trip units (MN, MX). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine, ATEX), Green Premium compliant (RoHS/REACh).
View AllClose